c
2024 Sun Hydraulics 1 of 5
MODEL
PRDF
Electro-proportional, direct-acting, pressure reducing/relieving valve with open
transition (740 Series)
SERIES 1 / CAPACITY: 20 L/min. / CAVITY: T-11A
M-Control
X-Control
NOTE: DATA MAY VARY BY CONFIGURATION. SEE CONFIGURATION SECTION.
This electro-proportional, direct-acting reducer/reliever valve reduces a high primary pressure at the inlet (port 2) to
a constant reduced pressure at port 1, with a full flow relief function from port 1 to tank (port 3). The valve is biased
to the relieving mode. Energizing the coil connects port 2 to port 1. Increasing the current to the coil will
proportionally increase the reduced pressure at port 1. If pressure at port 1 exceeds the setting induced by the coil,
pressure at port 1 is relieved to port 3. This valve is open in the transition from reducing to relieving. It provides
good pressure control and dynamic response. Optional full manual control is available.
This valve is designed to be used with 740 and 747 Series coils.
TECHNICAL DATA
Cavity T-11A
Series 1
Capacity 20 L/min.
Maximum Operating Pressure 350 bar
Maximum Valve Leakage at 110 SUS (24 cSt) 550 cc/min.
Solenoid Tube Diameter 16 mm
Valve Hex Size 22,2 mm
Valve Installation Torque 41 - 47 Nm
Model Weight (with coil) 0,55 kg
Seal kit - Cartridge Buna: 990511007
Seal kit - Cartridge Viton: 990611006
Seal and nut kit - Coil Viton: 990740006
Model Weight 0.26 kg.
PROPORTIONAL PERFORMANCE DATA
Hysteresis (with dither) 6%
Hysteresis with DC input <8%
Linearity (with dither) <2%
Repeatability (with dither) <2%
Recommended dither frequency 140 Hz
sunhydraulics.com/model/
PRDF
NOTES
Please verify cartridge clearance requirements when choosing a Sun manifold. Different valve controls and coils require different clearances.
An additional 2.00 inches (50,8 mm) beyond the valve extension is needed for coil installation and removal.
c
2024 Sun Hydraulics 2 of 5
(M)CONTROL
M Manual Override (Standard)
X No Manual Override
(D)OPERATING RANGE
D 50 - 485 psi (3,5 - 33,5 bar)
B 100 - 1125 psi (7 - 77,5 bar)
E 25 - 250 psi (1,7 - 18 bar)
S 10 - 100 psi (0,7 - 7 bar)
(N)SEAL MATERIAL
N Buna-N
E EPDM
V Viton
COIL *
No coil
* Additional coil options are available
TECHNICAL FEATURES
Maximum pressure at port 3 should be limited to 3000 psi (210 bar).
The transition from reducing to relieving is slightly open. The result is very good pressure control with oil consumption of about 0.1 gpm (0,4 L/min.). The relatively
high pilot control flow is only a factor in a dead-headed condition.
Pressure at port 3 is directly additive to the valve setting at a 1:1 ratio and should not exceed 3000 psi (210 bar).
For optimum performance, an amplifier with current sensing and adjustable dither should be used. Dither should be adjustable between 100 - 250 Hz.
NOTE: There is no upper limit to the pressure setting when using the M control. The more force you exert on the manual override, the higher the resulting pressure.
Full reverse flow from reduced pressure (port 1) to inlet (port 2) may cause the main spool to close. If reverse free flow is required in the circuit, consider adding a
separate check valve to the circuit.
Fully compatible with the XMD Expandable Mobile Drivers from Sun.
Direct acting concept provides highly reliable operation in contaminated systems, especially at dead headed conditions.
All three-port pressure reducing and reducing/relieving cartridges are physically interchangeable (i.e. same flow path, same cavity for a given frame size). When
considering mounting configurations, it is sometimes recommended that a full capacity return line (port 3) be used with reducing/relieving cartridges.
Incorporates the Sun floating style construction to minimize the possibility of internal parts binding due to excessive installation torque and/or cavity/cartridge
machining variations.
PERFORMANCE CURVES
Model Code Example: PRDFMDNCONFIGURATION OPTIONS
c
2024 Sun Hydraulics 3 of 5
c
2024 Sun Hydraulics 4 of 5
c
2024 Sun Hydraulics 5 of 5