Bulletin HY11-5715-592/UK
Proportional DC Valve
Installation Manual
Series D*1FH
Design ≥ 42
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Gutenbergstr. 38
41564 Kaarst, Germany
Tel.: +49-181 99 44 43 0
Fax: +49-2131-513-230
E-mail: infohcd@parker.com
Copyright © 2006,
Parker Hannifin GmbH & Co. KG
Proportional DC Valve
Series D*1FH
2
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Contents Page
1. Introduction 3
Characteristics 4
2. Technical Data 4
Parameters
Block Diagram Valve Electronics
Wiring
EMV
4
5
5
5
3. Installation 6
Electrical Connection 6
4. Switching Circuitry 7
Block Diagram
Set Value Input
Min/Max Setting
Diagnostic Output
Position Control
Power Stage
Enable Signal Input
Voltage Monitor
Control Failure Monitor
7
8
8
8
8
9
9
10
10
5. Measuring Points 10
Main (Central) Connector
Diagnostic Sockets
11
11
6. Commissioning 11
Ambient Conditions
Input Circuitry
Enable Signal
Zero Point Equalising
11
11
12
12
7. Service 14
Test Unit
Trouble Shooting Diagram
Replacing The Electronic Unit
14
15
16
8. Ordering Code 17
Note
This document and other information from Parker Hannifin GmbH & Co. KG, its sub-
sidiaries, sales offices and authorized distributors provide product or system options
for further investigation by users having technical expertise. Before you select or use
any product or system it is important that you analyse all aspects of your application
and review the information concerning the product or system in the current product
catalogue. Due to the variety of operating conditions and applications for these prod-
ucts or systems, the user, through his own analysis and testing, is solely responsible
for making the final selection of the products and systems and assuring that all per-
formance and safety requirements of the application are met. The products are
subject to change by Parker Hannifin GmbH & Co. KG at any time without notice.
Proportional DC Valve
Series D*1FH
Installation Manual
3
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
1. Introduction
D*1FH
Parker D**FH proportional directional control valves
are equiped with high dynamically powered sole-
noids and on-board electronics. The valve can be
linked to any signal control system (i.e. PLC) by
only one central plug and wiring connection.
The D*1FH series have a four-hole mounting sur-
face according to CETOP and a spool with four flow
path edges for standard applications.
Mechanical null adjustment to optimize
the zero overlap spool position (servo)
Proportional DC Valve
Series D*1FH
4
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Characteristics
The valve electronics described in this documenta-
tion relates to the control of high response direc-
tional control valves with solenoids, series D**F.
The electronics is an integrad part of the valve,
unifying various functions necessary for the opti-
mum usage of the valve and leading to an inte-
grated solution. The result is an outstanding dy-
namic response, permitting the valve to be used in
closed loop controls. The integrated electronics
carry out the following functions:
• Provides a specially designed output power
stage for high dynamic control of the solenoids
• Constant current control of the solenoids
• Overriding main stage stroke control
• Specially developed position transducer for high
resolution high dynamic control
• Differential input stage
All the information have been carefully selected
and assembled and represents the actual knowl-
edge.
General
Orientation Optional
Temperature drift of zero 0,005 % stroke/
0
C
Ambient temperature range [°C] -20 ... +60
Hydraulics
Hydraulic fluid Hydraulic oil according to DIN 51524 ... 535
Viscosity [mm²/s] 30 ... 80
Fluid temperature max. [°C] 0 ... 60
Electrical
Supply voltage [VDC] 18 ... 30
Ripple max. 5% eff.; noninductive
Switch-on current [A] 7.0 for 0.5mS (typ.)
Current consumption max. [A] 2.0
Fuse, to be provided externally [A] 2.5 medium time lag
Input signal [V] 0 ... ±10V smoothed, noninductive*
optional 0 ... ±20mA / 4...20mA*
Input impedance [kOhm] 200 (at current input 500Ohm)
Resolution sensitivty [mV] 5
Protection standard IP 65
Connection cable [mm²] 7 x AWG 17 (1.0 mm
2
), shielded
Cable length max. [m] 50
2. Technical Data
*max. 30VDC against Pin G (ground)
• Min/Max setting for valve operation conditioning
• Diagnostic output for valve stroke
• Enable signal for power output stage
• Low voltage monitoring of the supply voltage with
indicating lights giving operation status
• Standard central plug connection, DIN 43563
• Spindle operated trimpots for zero setting equal-
ising
• All electronics completely interchangeable
• Full conformity to the European EMC standards
Proportional DC Valve
Series D*1FH
Installation Manual
5
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Block Diagram Valve Electronics
Wiring
EN 50081-2 EN 55011
EN 50082-2 ENV 50140 EN 61000-4-4
ENV 50204 EN 61000-4-5
EN 61000-4-2 EN 61000-4-6
EMV
Proportional DC Valve
Series D*1FH
6
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Power Supply
The utilized power supply has to comply with the
EMC-standards (CE-sign, certificate of conformity).
Parker is offering the following power supplies:
Relais and solenoids operating from the same
supply circuit as the valve electronics has to be
fitted by surge protection elements.
Wiring Cable
The wiring cable between the control cabinet and
the valve has to be shielded. The central wiring has
to be installed from a 7wire cable that utilizes a
common shielding and a cross section of min.
AWG17. The capacity should not exceed a value
of approx. 130pF/m (wire/wire). The maximum
cable length is 50m. No power current lines may
be placed in parallel to the valve´s wiring cables.
The cable shield has to be connected to earth
ground at both ends (see also chapter “Ground-
ing“). Please be aware of ground-loops.
INSTALLATION GUIDE
TO PROVISION OF ELECTROMAGNETIC COMPATIBILITY
Connectors
The central connection of the valve electronics
needs a connector 6pin+E according DIN 43563
featuring metal case and integrated cable shield
coupling. Parker can provide suitable connectors:
5004072 (Connector 6pin+E)
The connectors have to be installed according the
connection diagram, the cable shield has to be tied
on the whole periphery to the provided coupling
clamp.
Grounding
The mounting plate of the valve has to be con-
nected to the grounded metal machine frame. The
Earth wire to pin G of the central wire cable as well
as the cable shields of the valve connection cables
should be tied to earth ground at the control cabi-
net. A low-ohmic potential compensation wire has
to be provided between the control cabinet and the
machine frame (cable wire >AWG7
cross section)
to prevent ground loops.
The connecting cable has to comply to the follow-
ing specification:
Cable type control cable, flexible,
7 conductors, overall braid
shield
Cross section min. AWG16
Outer dimension 8...12 mm
Cable length max. 50 m
For cable lengths > 50 m consult factory.
The connection cable is coupled to the female
connector by solder joints.
Skinning lengths for the connecting cable:
3. Installation
Electrical Connection
The electrical connection of the valve takes place
by one common cable, which is coupled to the in-
tegrated electronic driver by a central connector
assembly.
The connection requires a 6 + PE female connec-
tor EN 175201-804.
The female connector has to be ordered
separately under article nr. 5004072.
A female connector with metal housing is
required! Plastic made models may create
function problems due to insufficient EMC-
characteristics.
Proportional DC Valve
Series D*1FH
Installation Manual
7
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
4. Switching Circuitry
Block Diagram
Proportional DC Valve
Series D*1FH
8
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Signal-Input
The command signal input of the valve has been
wired from the connector terminals D and E to the
differential input of the onboard electronic. The
valve stroke is acting proportional to the value of
the signal. According to the valve model there are
different command signal options available, which
are separately described below. More details are
obvious from the technical data. The input signal
must be filtered as well as free of surges and
modulations. Due to the resolution sensitivity a high
signal quality is recommended, to avoid function
disturbances.
Improper high signal amplitudes may lead to
function disturbances or damaging depend-
ing of the exceeding value.
The explanation of functionality assumes
junction E as point of reference potential.
Wiring example of voltage input option +10...0...-10 V
Wiring example of current input option 4...12...20 mA
Wiring example of current input option +20...0...-20 mA
Command signal option 4...20 mA uses the “0 mA“
- condition as failure information. This means that
an evaluable failure information is provided for an
interrupted command signal circuit. In the present
case the solenoid drive thereby will be switched off.
The drive will be activated if the input signal ex-
ceeds a value of 3,8 mA and will be disabled below
3,6 mA. This definition follows the NAMUR standard
NE43.
Proportional DC Valve
Series D*1FH
Installation Manual
9
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Min/Max-Setting
The min/max-setting option achieves a conditioning
of the valve operating range to a certain application.
The min-setting is used for valves with overlapped
main spools, it compensates for the mechanical
overlap by an offset-feature.
The max-setting limits the stroke of the valve spool,
equally the full input signal range will be preserved
and can be used with full resolution.
Both settings are provided separately for both valve
operating directions.
Diagnostic Output
To make available measurements for the momen-
tary position of the valve spool the valve electron-
ics unit provides a diagnostic output. This is avail-
able at the main connector between pin F and
supply zero (pin B) as well as on the printed circuit
board of the valve electronics unit which provides
two diagnostic sockets. The sockets take 2mm
plugs and can e.g. be used in the setting up of the
zero point.
The output is a 0...±10V signal where the value of
10V normally represents the maximum permitted
stroke of the valve spool.
The diagnostic output is short circuit proofed and
is fully operative up to a load of at least 2kOhms
or 5mA.
Position Control
The purpose of the position controller is to compare
the actual value of the spool as given by the valve
electronics sensor with the set value and provide
signals to the actuating solenoids to ensure that
the set position is achieved and maintained. The
sketch below shows the operating principle of the
control circuit.
Power Stage
In the output stage the output signal of the position
controller is converted into an activating signal for
the operating solenoids.
Keeping the power relationships at the solenoid
constant as well as the need for rapid excitation of
the solenoids is achieved with controlled current
from a constant current control stage.The solenoid
current is measured in the valve electronic unit and
compared with the set-value for current in the
constant current controller. As long as there is a
difference between set and actual current values
the output stage will change the solenoid current
in order to equalise them.The solenoid also has a
superimposed dither signal which has been care-
fully matched with the mechanics of the valve to
compensate for mechanical friction so that the
hysteresis will not influence the dynamics of the
valve.
Enable Signal Input
To switch-off the output stage the valve electronics
unit is fitted with an enable signal input which can
at any time be used to interrupt the solenoid current
irrespective of transducer signal or set value. In this
case the main spool takes up - without any delay
- the spring centered position in the valve.
A further function of the enable signal input is to
limit the output of the position control. Normally on
switching off the activated solenoid the output of
the controller would be driven into saturation by the
Integral part of the PID system. Because of this, if
the solenoid is immediately switched on again the
valve spool is for a short period of time operated
indefinetily. To avoid this, the integral part of the
controller is switched out and a limit is placed on
the controller output for as long as the enable input
is switched off. When the enable signal is switched
on again the valve spool will immediately move
from it's central position and take up the required
set position.
The enable signal input is, as far as circuitry is
concerned, completely isolated from the rest of the
electronics to keep interference from peripheral
equipment away from valve electronic unit. It re-
quires a signal in the region of 5 to 30VDC with a
current supply of about 10mA. The enable signal
is fed into the unit via the central connector between
pins B and C.
Proportional DC Valve
Series D*1FH
10
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
5. Measuring Points
Note
Position Of The Measuring Points
Measurements as described at the points shown
on the diagram below may only be made by
experienced personnel (electronic) to ensure
that damage is not done to the valve electronic
unit.
The enable signal should preferably be switched
off together with the hydraulic pressure source in
order that the solenoid spools have no circulating
current when the hydraulic system is switched off.
This reduces energy loss and unnecessary heat
generation in the solenoid spools.
Note
The enable signal does not provide security against
unwanted operation of a valve in the sense of the
accident prevention regulations. To block all pos-
sibility of a valve functioning under any circum-
stances, further steps are necessary, e.g the fitting
of safety lock valves.
Voltage Monitor
The supply voltage may therefore lie between 18
and 30V, with a ripple of no more than 5%. These
voltages are valid on load i.e. with valve electronics
and enable signal connected.
The value of the supply voltage is supervised by
an integrated voltage monitoring.
Control Failure Monitor
If a failure >2% occurs within the position control
loop of the valve a control failure signal is given.
This is the case, if the valve spool does not reach
the predetermined position. The most important
reasons for this behaviour could be:
• No or too low pilot presssure
• Blocking or defective valve mechanics by dirt
• No enable signal
• Input signal failure (only for option 4...20mA)
The operating condition of the monitoring is indi-
cated by a dual color LED within the valve electron-
ics cover.
An explanation of the light indicator is printed on
the placard on the cover.
Function
Pin B: 0V Pin C: 0V Output disabled
Pin B: 0V Pin C: 5...30V Output enabled
Indicator green
Normal operation
Indicator off
Supply voltage is outside the
normal range
Indicator red
Control failure
Proportional DC Valve
Series D*1FH
Installation Manual
11
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Pin
Signal level
representing
Measurement/
range
A
Plus level
Supply voltage
+18...30V
measured against
pin B
B
Reference potential Reference
C
Enable signal
+5...30V
measured against
pin B
D
Command signal
+0...10V
measured against
pin E
E
Command signal
-0...10V
measured against
pin D
F
Diagnostic signal
valve stroke
±0...10V
measured against
pin B
G
Connection to
ground
–
Main (Central) Connector
The normal operating voltage levels for the valve
electronic unit are available through the central
connector.
In particular, the following individual possibilities
are available:
6. Commissioning
Ambient Conditions
The valve electronics unit has been designed to
work reliably together with the hydraulic valve as a
unit under normal industry conditions. It is pro-
tected against environmental influences by its cast
iron housing which also prevents the entry of for-
eign particles and is sealed against the entry of
water.The electronics are partly encapsulated and
have a protective coating of varnish.
Even so, mechanical loading of the electronics box
as well as its use outside of the following installation
conditions is not allowed as permanent damage or
a reduction in working life cannot be ruled out. It is
advisable to install the unit directly by the machine,
protected from extreme environmental influences.
Input Circuitry
The differential input of the valve electronic unit
ensures a freedom from input problems with the
user’s set value signals.
Command Signal Control System
There are three basic variations on set value con-
trol:
• Take the set value signal from a programmable
logic control unit (PLC).
• Set value control through interface electronics.
• Set value signals from preswitched controller.
Connection
Signal level
representing
Measurement
value/range
Testpoint 1
yellow
outer
Diagnostic signal
valve stroke
±0...10V
measured against
testpoint 2
Testpoint 2
yellow
inner
reference
potential
–
Diagnostic sockets
The diagnostic sockets are for the purpose of
measuring the actual stroke of the valve. A correla-
tion table.
Proportional DC Valve
Series D*1FH
12
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Adjustment Of The Mechanical Zero Point
(zero lap spools only)
Tools
Allen Key SW6
Wrench SW19
Conditions
Valve electronics unit switched off, hydraulics work-
ing.
Adjustment
1. Loosen locking cover nut of the adjusting spindle.
2. Adjust the zero point until the actuator is in the
neutral position or takes up the desired creep
position.
3. Replace cover nut.
The following command signal value results in the
electrical zero point of the valve:
Enable Signal
The valve electronic unit uses an “enable” signal
function in the range of 5...30V at pin C of the main
connector (see chapter “Enable Signal Input“).
There are two different ways of controlling the en-
able signal input:
• Using the 24V supply voltage through an enable
switch provided by the user.
• Feeding the enable signal from a control system
of the user with the reference (zero) point of the
user's control connected to pin B of the central
connector and the enable signal is connected to
pin C.
The enable signal must only be switched on to
the valve electronics unit when the valve is to be
used; all other times should be off.
Example: Start-up of a hydraulic control system
As against the supply voltage, which will be switched
on at the same time as the hydraulic system, the
enable signal should preferably not be switched on
until the hydraulic system has reached full pressure.
This will prevent any system disturbance.
Zero Point Equalising
The main valve spool takes up the spring-centred
position if the power fails or the enable signal has
not been given. Valves with overlap spools have a
factory adjusted zero point. Valves with zero lap
spools usually have mechanical centering. In this
case there is a possibility of the operating condi-
tions allowing the activated device e.g a cylinder,
to creep in an uncontrolled direction; the valve
electronics unit takes account of this possibility and
allows the creeping movement in a predefined di-
rection only.
Valves with overlapping type spools are factory-
preset to null. In the case of valves with zero lap
spools it is necessary for the user to adjust the
electrical zero point in accordance with its require-
ments. The adjusting can be done via a selflocking
spindle trimmer in the valve electronic unit. The
position of the trimmer is shown on the placard on
the cover.
Adjustment spindle for setting
zero (centered) position
Electronic variation B E S
Command signal 0V 0mA 12mA
Proportional DC Valve
Series D*1FH
Installation Manual
13
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Equalising The Electrical Zero Point
Conditions
Mechanical zero point adjustment has been done.
Valve electronic unit is working. Enable signal has
been applied. Hydraulics working.
Adjustment
Using the zero point spindle-trimmer until the drive
remains in the rest position.
Set Up Of The Min/Max-Setting
(overlapped spools only)
Tools
Allen Key SW3
Screwdriver 2mm
First remove the locked cover of the valve elec-
tronic unit. The position of the trimpots is shown on
a sticker on the internal side of the valve electron-
ics cover.
Adjustment
1. Feed in a command signal:
2. Adjust offset for corresponding valve side by
potentiometer “min b“ (P5). (increasing = turn
clockwise).
3. Feed in a command signal:
Electronic variation B E S
Command signal 0V 0mA 12mA
Electronic variation B E S
Command signal +50mV +0.1mA 11.96mA
Electronic variation B E S
Command signal +10V +20mA +4mA
Electronic variation B E S
Command signal +10V +20mA +4mA
Electronic variation B E S
Command signal -10V -20mA +20mA
4. Adjust the required spool stroke for correspond-
ing valve side by potentiometer “max b“ (P7).
(increasing = turn clockwise).
5. Repeat that procedure for opposite valve side.
Feeding in negative command signals with the
same set up procedure by using potentiometers
“min a“ (P6) as well as “max a“ (P8).
6. Take into account that min has to be adjusted
before max.
Set Up Of The Max-Setting
(zero lap spools only)
The position of the trimpots is shown on a sticker
on the internal side of the valve electronics cover.
1. Check if the potentiometers “min a“ (P6) and “min
b“ (P7) are in their end position (fully counter-
clockwise).
2. Feed in a command signal:
3. Adjust the required spool stroke for correspond-
ing valve side by potentiometer “max b“ (P7)
(increasing = turn clockwise).
4. Feed in a command signal:
5. Adjust the required spool stroke for opposite
valve side by potentiometer “max a“ (P8).
6. At last replace cover and seal.
Proportional DC Valve
Series D*1FH
14
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Test Unit EX00-M03
The test unit EX00-M03 is usable for the control of
proportional valves incorporating integrated elec-
tronics. It provides commissioning and function test
independently from the machine control system.
The test unit is provided with all necessary signal
and measurement taps, making it possible to pro-
ceed initial operation and diagnosis.
Technical Data
• Control of valves incorporating integrated elec-
tronics and central plug acc. to DIN 43563
(6pin+PE)
• Main connection selectable 230/115VAC
• Build-in fuses
• Cordset included
• Integrated digital voltmeter with test point selec-
tor switch
• Test jacks
• Rugged metal enclosure with handles
7. Service
Commissioning Help
When commissioning a valve installed on a ma-
chine control unit the following question is fre-
quently asked:
How can we operate the valve by hand independ-
ently of the overall control system to e.g. to adjust
the zero point or to set-up a newly installed cylin-
der?
An appropriate test unit is available by order no.
EX00-M03.
Operator Panel
1 Voltage readout
2 Test point selector switch
3 Switch enable on/off
4 Command signal potentiometer V+
5 Command input selector switch
6 Command signal potentiometer V-
7 Fuse 3A 24VDC
8 Power indicator
9 Test jacks
10 Main input 230/115VAC
11 Main switch
12 Voltage selector / main fuse
13 Valve control output socket
Proportional DC Valve
Series D*1FH
Installation Manual
15
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Trouble Shooting Diagram
Proportional DC Valve
Series D*1FH
16
Installation Manual
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Replacing The Electronic Unit
In case of a fault in the electronic unit the complete
unit must be replaced.
Replacing The Electronic Printed Circuit Board
Tools
Allen key SW3
Conditions
Hydraulics switched off.
Remove central connector; ensure unit voltage
supply is off.
Exercise great care when taking parts out and keep
them safe.
Replacement
1. Remove the closing cover on the back end of
the electronic box
2. Loosen plug s1 (Fig. 1)
3. Using the Allen key SW3 remove the fixing nut
of the displacement transducer. Keep the fixings
safe. (Fig. 2)
4. Remove the printed circuit board from the box
without using force
5. Install the new printed circuit board. The type can
be seen on a type label
6. Install in reverse order to the dismantling proce-
dure
7. Re-do the electrical zero point as well as the
min/max-setting
8. Apply the closing cover including the seal.
Tighten the bolts M4/DIN912-8.8 so that the
cover fits tightly on the box
Fig. 1
Transducer And Connecting Socket
Fig. 2
Fixing Components Of Transducer
Proportional DC Valve
Series D*1FH
Installation Manual
17
IA HY11-5715-592 D1FH KS42 UK.INDD CM
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
8. Ordering Code
D*1FH
DC
valve
Spool
type
FlowNominal
size
Valve
accessories
Pilot oil
guide
Seal
Electronic
variation
Design
series
Flow
control
High
Response
Central connector not included
1)
with enlarged connections
Ø 32mm
3)
only for spools with positive
overlapping
2)
not for D111FH
4)
only for E50 / B60
Code
Flow [l/min] at
∆p 5bar per flow path
D31
4)
D31 D41 D81/91 D111
A 20/33 55 – – –
B – – 105 – –
C 32/55 80 140 – –
E – – 190 250 –
F – – 240 310 –
H – – – 400 500
L – – – – 1000
D
F
H1
0
Code Spool type
Overlap
E01
E02
B31
Q
B
= Q
A
/2
B32
Q
B
= Q
A
/2
B11
B12
Zerolap
2)
E52
B61
Q
B
= Q
A
/2
Code Nominal size
3 NG10 / CETOP 5
4 NG16 / CETOP 7
8 NG25 / CETOP 8
9
1)
NG25 / CETOP 8
11 NG32 / CETOP 10
Code Valve accessories
0 Standard
8
3)
Monitor switch
Code Inlet Drain
1 internal external
2 external external
4 internal internal
5 external internal
Code Electronic variation
B
Voltage input
0...±10V standard
E
Current input
0...±20mA
S
Current input
4...20mA
Code Seal
N NBR
V FPM