E 5.805.3 / 08.16
1
Air Cooler Mobile
OK-ELD 0-6
with DC motor
General
The OK-ELD air cooler series is
designed
specically for mobile hydraulic
applications
where high performance
and efciency are required and physical
size must be minimized to allow easy
installation.
Product Features
These coolers use a combination of high
performance cooling elements and high
capacity, long life DC electric powered
fans to give long trouble free operation
in arduous mobile hydraulic applications.
The compact design allows the coolers
to t most equipment and provide the
highest cooling performance in heat dissi-
pation whilst minimizing space required.
l Compact, efcient, high performance
l Cooling range 2 - 34 kW
l DC motors in 12 Volt and 24 Volt with
motor lifetimes up to 16,000 hours
Application Field
Hydraulic systems in mobile machines
and vehicles, such as
l Mobile cranes
l Concrete mixers and pump trucks
l Road paving machines
l Construction machines
(excavators, wheel loaders)
l Agricultural machines
l Municipal machines
Symbol
Operation Data
Fluids l Oils (mineral oils, synthetic oils, high viscosity oils,
biological oils, phosphate ester)
l Water-glycol (cooling uids)
l HFC pressure uids
Viscosity 2,000 mm²/s (standard)
Temperature range l Minimum / maximum ambient temperature:
- 20 °C to + 40 °C (standard)
l Minimum / maximum temperature of the medium:
+ 20 °C to + 130 °C
Please contact the technical sales department in the event
of deviating temperatures.
Notice!
Fan at max. speed (max. volume of air) must be avoided when
operating a cooler at which the temperature difference between
the medium inlet at the cooler and the ambient temperature
can be greater than 50 °C. Quick changes in the temperature of
the cooling element material can lead to a signicant reduction in
service life or to direct damage of the cooling element due to
thermal shock.
Please contact the technical sales department to receive
information about controlled fan drives.
Pressure resistance
of the cooling element
l Dynamic operating pressure: 16 bar
l Static operating pressure: 21 bar
Fan Axial fan in suction version (standard)
Axial fan in pushing version on request
(note: approx. 10 % less cooling capacity)
Motor l DC motor
l 12 V / 24 V
l Protection class IP68
l Insulation class F
Other versions on request.
Noise levels See technical data
The noise levels are only reference values as the acoustic
properties of a room, connections and reection have an effect
on the noise level.
Accessories l Integrated pressure bypass valve (IBP) or
integrated thermal pressure bypass valve (IBT)
(cannot be retrotted, also see options)
l Brushless fan
l Electronic speed control (ESC)
l Thermostats
l Air lter grid or air lter mat
l Vibration damper
E 5.805.3 / 08.16
2
3
2
1
Options
Integrated pressure bypass
valve (IBP) / Integrated thermal
pressure bypass valve (IBT)
The bypass channel is integrated in the
cooling element. If a particular pressure
is exceeded, the IBP opens the bypass
channel, thereby protecting the cooling
element from too high a pressure.
Furthermore, the IBT only opens the
cooling element path once a particular
temperature has been reached.
Design
OK-ELD 0
OK-ELD 1.5
3
2
1
Air cooler with
1 Axial fan with integrated motor
2 Fan housing
3 Heat exchanger
Air cooler with
1 Axial fan with integrated motor
2 Fan housing
3 Heat exchanger
E 5.805.3 / 08.16
3
Design
OK-ELD 1- 4.5
OK-ELD 5-6
3
2
1
3
2
1
Air cooler with
1 Axial fan with integrated motor
2 Fan housing
3 Heat exchanger
Air cooler with
1 Axial fan with integrated motor
2 Fan housing
3 Heat exchanger
E 5.805.3 / 08.16
4
Technical Data
OK-ELD 0-6
Type of cooler
P/N
Voltage [V]
Fluid ow [l/min]
1)
Air ow [m
3
/h]
Fan motor:
Power / current absorption
[kW / A]
2)
Recommended Fuse
[A]
Fan Diameter [mm]
2)
Noise level (at 1 m distance)
[dB(A)]
Volume [l]
3)
Weight [kg]
4)
kW A
OK-ELD 0 3169981 12 60 279 0.05 3.0 5.0 140 68 0.4 2.7
OK-ELD 0 3169980 24 60 279 0.05 1.6 5.0 140 68 0.4 2.7
OK-ELD 1 3083371 12 150 451 0.10 8.0 15.0 190 73 0.6 4.0
OK-ELD 1 3083596 24 150 451 0.10 3.2 7.5 190 73 0.6 4.0
OK-ELD 1.5 3106405 12 150 455 0.10 8.0 15.0 190 77 1.0 4.7
OK-ELD 1.5 3106406 24 150 455 0.10 4.0 7.5 190 77 1.0 4.7
OK-ELD 2 3083370 12 150 910 0.14 9.4 20.0 255 74 2.0 9.4
OK-ELD 2 3083597 24 150 910 0.14 5.2 15.0 255 74 2.0 9.4
OK-ELD 3 3083369 12 180 1,338 0.23 17.5 25.0 305 79 2.2 11.0
OK-ELD 3 3083678 24 180 1,338 0.23 8.0 20.0 305 79 2.2 11.0
OK-ELD 4 3809511 12 180 2,052 0.30 22.5 30.0 385 76 3.0 15.9
OK-ELD 4 3809078 24 180 2,052 0.30 10.5 20.0 385 76 3.0 15.9
OK-ELD 4.5 3979800 12 180 2,284 0.30 22.5 30.0 385 76 5.2 22.0
OK-ELD 4.5 3979801 24 180 2,284 0.30 10.5 20.0 385 76 5.2 22.0
OK-ELD 5 3083286 12 180 3,581 0.46 35.0 2 x 25 305 80 4.2 30.3
OK-ELD 5 3083681 24 180 3,581 0.46 16.0 2 x 20 305 80 4.2 30.3
OK-ELD 6 3982479 12 180 5,020 0.60 45.0 2 x 30 385 77 5.2 36.6
OK-ELD 6 3982420 24 180 5,020 0.60 21.0 2 x 20 385 77 5.2 36.6
1)
Max. ow rate
2)
OK-ELD 5-6: each fan
3)
Fluid in cooling element
4)
Unlled
Counter connector
Type of cooler P/N
OK-ELD 0
12 V 3973604
24 V 3973656
OK-ELD 1 12 V / 24 V 3973602
OK-ELD 1.5 12 V / 24 V 3973602
OK-ELD 2 12 V / 24 V 3973602
OK-ELD 3 12 V / 24 V 3176990
OK-ELD 4 12 V / 24 V 3973602
OK-ELD 4.5 12 V / 24 V 3973602
OK-ELD 5 12 V / 24 V (2x) 3176990
OK-ELD 6 12 V / 24 V (2x) 3973602
E 5.805.3 / 08.16
5
Cooling Capacity and Pressure Difference Δp
OK-ELD 0-6
Pressure difference Δp
Cooling capacity:
Dependent on the oil ow rate and
the temperature difference ΔT between
oil inlet and air inlet.
Note:
The values are measured at
ΔT = 40 °C. For smaller ΔT values,
the values can change. You can also use
our cooler calculation software
for designing. Please contact our
technical sales department.
Heat dissipation @ ΔT = 40 °C [kW]
Tolerance: ± 5 %
Oil ow [l/min]
Specic heat dissipation [kW/K]
For other viscosities, the pressure loss must be multiplied
by the conversion factor K:
Viscosity (mm²/s) 10 15 22 30 46 68 100 150
Factor K 0.35 0.5 0.75 1.0 1.4 1.9 2.5 3.5
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
0 20 40 60 80 100 120 140 160 180 200
Oil ow [l/min]
Pressure drop [bar]
measured at 30 mm²/s
Tolerance: ±5 %
OK-ELD 0 OK-ELD 0 OK-ELD 1.5
OK-ELD 6
OK-ELD 5
OK-ELD 4
OK-ELD 2
OK-ELD 3
OK-ELD 4.5
40
36
32
28
24
20
16
12
8
4
0
1,0
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
0 20 40 60 80 100 120 140 160 180 200
OK-ELD 5
OK-ELD 6
OK-ELD 3
OK-ELD 4
OK-ELD 4.5
OK-ELD 2
OK-ELD 1.5
OK-ELD 1
OK-ELD 0
E 5.805.3 / 08.16
6
Model Type
OK-ELD - 1H - 3.1 - 12 VBL - 1 - S - AITF60
Cooler type
OK-ELD = Oil-Air cooler
Size / motor speed
0-6 = size
H = 2 pl (3,000 min
-1
)
Revision
Motor voltage
12 V = 12 V DC
24 V = 24 V DC
12 VBL = 12 V DC brushless
24 VBL = 24 V DC brushless
Color
1 = RAL 9005 (standard)
Other colors on request.
Air ow direction
S = Suction (standard)
D = Blowing
Accessories
IBP = Heat exchanger with integrated bypass valve
IBT = Heat exchanger with integrated thermo-bypass valve
AITF = Thermostat (xed)
ESC = Electronic speed control
For all possible accessories, like vibration absorber, air lter grid or air lter mat,
please refer to brochure Accessories for air coolers.
E 5.805.3 / 08.16
7
Dimensions
OK-ELD 0
Dimensions
OK-ELD 1.5
A/2 A/2
E2
E4
A
(4x) Ø F
E3
B
E1 Z3
ROTATION
C
Z1 (2x)
E5
AIR
AIR
A/2 A/2
E2 E1
A
(4x) Ø FE4
B
E3
ROTATION
C
Z1 (2x)
E5
AIR
AIR
E 5.805.3 / 08.16
8
[mm]
A
±5
B
± 10
C
±5
E1
± 5
E2
± 5
E3
± 5
E4
± 5
E5
± 2
F
ø / slot
Z1 Z3
OK-ELD 0 202 140 240 72 79 10 60 190 6.5 G½" –
OK-ELD 1 245 120 300 125 60 250 225 180
1)
9.0 M22x1.5 M22x1.5
OK-ELD 1.5 217 137 330 43 172 255 121 40 M8 M22x1.5 M14x1.5
OK-ELD 2 313 207 384 199 57 324 288 80 14x10 G1" M22x1.5
OK-ELD 3 356 207 420 230 63 370 329 100 14x10 G1" M22x1.5
OK-ELD 4 450 208 500 300 75 445 421 150 19x10 G1" M22x1.5
2)
OK-ELD 4.5 454 227 602 350 52 495 200 580
1)
12.0 G1-¼" M22x1.5
2)
1)
OK-ELD 1 and OK-ELD 4.5 have only the four external xing points
2)
OK-ELD 4 and OK-ELD 4.5 have two connections M22x1.5
Dimensions
OK-ELD 1-4
A/2A/2
E1
E4
A
(6x) Ø F
E3
B
E2
Z3
ROTATION
C
Z1 (2x)
AIR
AIR
HYDAC
HYDAC
E 5.805.3 / 08.16
9
Note:
We recommend maintaining a minimum
distance to ensure an unimpeded air
inlet and air outlet. This is half the
height of the cooling element (A/2).
Anything below the minimum distance
can inuence the cooling capacity and
the noise emissions.
Dimensions
OK-ELD 5-6
[mm]
A
±5
B
± 10
C
±5
E1
± 5
E2
± 5
E3
± 5
E4
± 5
E5
± 2
F
ø / slot
Z1 Z3
OK-ELD 5 480 232 810 321 79 750 450 170 10x20 G1-¼" M22x1.5
OK-ELD 6 532 233 950 373 81 888 503 200 9x21 G1-¼" M22x1.5
E5
E3
C
E5 E5
Z3
Z1 (2x)
A/2 A/2(8x) Ø F
B
E4
A
E1E2
HYDAC
ROTATION ROTATION
AIR
AIR
E 5.805.3 / 08.16
10
Note
The information in this brochure
relates to the operating conditions.
For applications and operating conditions
not described, please contact the
relevant technical department.
Subject to technical modications.
Industriegebiet
66280 Sulzbach/Saar
Germany
Tel.: +49 6897 509-01
Fax: +49 6897 509-454
Internet: www.hydac.com
Via Sceresa, Zona Industriale 3
6805 Mezzovico
Switzerland
Tel.: +41 91 9355-700
Fax: +41 91 9355-701
Internet: www.hydac.com
HYDAC COOLING GMBH
HYDAC AG
Mezzovico Branch