Series number
www.atos.com Table F160-18/E
DHZO-A* and DKZOR-A* are proportional
valves, direct operated without position
transducer, which provide both directional
and non-compensated flow control
according to the electronic reference
signal.
They operate in association with electronic
drivers, see section
쪨
, which supply the
proportional valves with proper current to
align valve regulation to the reference
signal supplied to the electronic driver.
They are available in different executions:
• -A, without position transducer;
• -AE, -AES as -A plus analogue (AE) or
digital (AES) integral electronics
햵
;
The 4-way spool
햳
, sliding into a
5-chambers body
햲
, is directly operated
by proportional solenoids
햴
.
The integral electronics
햵
ensures factory
presetting, fine functionality plus valve-to-
valve interchangeability and simplified
wiring and installation.
The electronic main connector 쩽 is fully
interchangeable for -AE and -AES
executions.
Standard 7 pin main connector is used for
power supply, analog input reference and
monitor signals.
12 pin connector is used for options /Z and
/W (AES).
Following communication interfaces
햷
,
햸
are available for the digital -AES execution:
• -PS, Serial communication interface for
configuration, monitoring and firmware
updating through Atos PC software -
always present also for -BC, -BP and -EH
options.
• -BC, CANopen interface
•
-BP, PROFIBUS DP interface
•
-EH, EtherCAT interface
The valves with -BC, -BP and -EH
interfaces can be integrated into a fieldbus
communication network and thus digitally
operated by the machine control unit.
The coils are fully plastic encapsulated
with insulation class H.
Mounting surface: ISO 4401 sizes 06 and 10
Max flow respectively up to 50 l/min and
105 l/min with valve differential pressure
Δp = 30 bar, see table
쪩
.
Max pressure = 350 bar for DHZO;
315 bar for DKZOR.
DHZO
DHZO
size 06
DKZOR
size 10
A = without position
transducer
AE = as A plus integral
electronics
AES = as A plus inte-
gral digital elec-
tronics
Valve size - ISO 4401
0 = size 06 1 = size 10
Spool overlapping in central position, see sect.
쪩
1 = P, A, B, T positive overlapping (20% of spool
stroke)
3 = P positive overlapping; (20% of spool stroke)
A, B, T, negative overlapping
Spool size: 14, 1, 3, 5 = see section
쪩
AES PS
07 -1S5/ /***/*---
1
MODEL CODE
F160
DKZOR-AES-BC-171-*
Communication interfaces
only for AES (1)
PS = Serial
BC = CANopen
BP = PROFIBUS DP
EH = EtherCAT
Configuration, see section
쪩
5 = external plus central position, spring
centered
7 = 3 position, spring centered
Proportional directional valves type DHZO-AES and DKZOR-AES
direct operated, without position transducer, ISO 4401 size 06 and 10
Spool type (regulating characteristics)
L = linear; S = progressive;
D = differential-progressive
(as S, but with P-A= Q, P-B= Q/2)
Valve body
Spool
Proportional solenoid
Integral electronics
Main connector
햲
햳
햴
햵
햶
2
ELECTRONIC DRIVERS FOR DHZO-A*
Valve model
Data sheet
Drivers model E-MI-AC-0*F
G010
E-BM-AS-PS
G030
E-ME-AC-0*F
G035
-A
-AES
-AE
E-RP-AC-0*F
G100
E-RI-AE
G110
E-RI-AES
G115
Hydraulic options, see section
쪬
:
B =solenoid and integral electronics
at side of port A
Y =external drain
Options for -A execution see sect. 쪭:
MO = horizontal hand lever
MV = vertical hand lever
BMO = horizontal hand lever instal-
led at side of port A
BMV = vertical hand lever installed
at side of port A
N = manual micrometric adjustment
NV = as N plus handwheel and gra-
duated scale
Electronics options for -AE execu-
tion see section
쪯
:
I =
current reference input (4÷20 mA)
Q=enable signal
Electronics options for -AES exe-
cution see section :
Q = enable signal
Z =double power supply, enable fault
and monitor (12 pin connector)
W = power limitation function (12 pin
connector) see section 11.3
11
-BC or -BP communication connector
-PS communication connector (3)
-EH Communication connector (input)
-EH Communication connector (output)
햷
햸
햹
햺
Note: (1) Serial communication interface always present, also for -BC, -BP and -EH options
Note: For power supply and communication connector see section 14
E-BM-AC-0*F
G025
E-MI-AS-IR
G020
*
Coil voltage (only for -A exe-
cution) see section 쪭:
- = standard coil for 24V
DC
Atos drivers
6 = optional coil for 12V
DC
Atos
drivers
18 = optional coil for low cur-
rent drivers
Seals material,
see section 쪪:
- =
NBR
PE = FKM
BT = HNBR
(only -A)
3
HYDRAULIC CHARACTERISTICS (based on mineral oil ISO VG 46 at 50 °C)
Valve model
DHZO
Spool type and size
Spool overlapping
Max flow (1) [l/min]
at
Δ
p = 10 bar (P-T)
at
Δ
p = 30 bar (P-T)
at
Δ
p = 70 bar (P-T)
Response time (2) [ms]
Hysteresis [%]
Repeatability
< 30
≤ 5%
± 1%
< 40
≤ 5%
± 1%
1
2
3
4,5
8
12
45
80
120
60
105
160
L14 L1
17
30
45
S3, L3, D3
28
50
74
S5, L5, D5 S3, L3, D3 S5, L5, D5
1, 3 1, 3 1, 3 1, 3 1, 3 1, 3
Hydraulic symbols
*71, *71/B *73, *73/B *51 *53 *51/B *53/B
b b b a a
a
a b
Notes:
앬
Above performance data refer to valves coupled with Atos electronic drivers, see section 쪨.
앬
The flow regulated by the directional proportional valves is not pressure compensated, thus it is affected by the load variations.To keep costant the
regulated flow under different load conditions, modular pressure compensators are available (see tab. D150).
(1) For different
Δ
p, the max flow is in accordance to the diagrams in sections 14.2 and 15.2
(2) 0-100% step signal
DKZOR
Pressure limits [bar] ports P, A, B = 350; T = 210 (250 with external drain /Y)
8
14
21
S2
1, 3
ports P, A, B = 315; T = 210 (250 /Y)
4
MAIN CHARACTERISTICS
6
HYDRAULIC OPTIONS
6.1 Option /B Solenoid (for valve configuration *5*), and integral electronics at side of port A. For hydraulic configuration vs. reference signal, see
section 14.1 and 15.1
6.2 Option /Y External drain advisable when the valve is used in double flow path, see section 14.5 and 15.5. Option /Y is mandatary if the pressure in
port T exceeds 160 bar.
DHZO and DKZOR proportional valves are CE marked according to the applicable Directives (e.g. Immunity/Emission EMC Directive and Low Voltage Directive).
Installation, wirings and start-up procedures must be performed according to the general prescriptions shown in table F003 and in the installation notes
supplied with relevant components.
The electrical signals of the valve (e.g. monitor signals) must not be directly used to activate safety functions, like to switch-ON/OFF the machine’s safety
components, as prescribed by the European standards (Safety requirements of fluid technology systems and components-hydraulics, EN-982).
5
GENERAL NOTES
8
CONNECTIONS FOR -A EXECUTION
Signal description
SUPPLY
SUPPLY
GND
PIN
1
2
3
SOLENOID POWER SUPPLY CONNECTOR
1
2
3
7
OPTIONS FOR -A EXECUTION
7.1 Option /6
optional coil to be used with Atos drivers with power supply 12 VDC
7.2 Option /18
optional coil to be used with electronic drivers not supplied by Atos
7.3 Auxiliary hand lever
this option is available only for DHZO-A with spool type S3, S5, D3, D5, L3, L5.
It allows to operate the valve in absence of electrical power supply. For detai-
led description of DHZO-A with hand lever option see table E138
앬
Option /MO horizontal hand lever
앬
Option /MV vertical hand lever
앬
Option /BMO horizontal hand lever installed at side of port A
앬
Option /BMV vertical hand lever installed at side of port A
The following supplementary options allow to operate the valve in absence of
electrical power supply by means of a micrometric screw replacing the stan-
dard solenoid manual override, see table TK500
7.4 Option /N manual micrometric adjustment
7.5 Option /NV as /N plus handwheel and graduated scale
Assembly position Any position
Subplate surface finishing Roughness index, Ra 0,4 flatness ratio 0,01/100 (ISO 1101)
MTTFd valves according to EN ISO 13849 150 years, for further details, see technical table P004
-A execution = -20°C ÷ +70°C (storage -20°C ÷ +80°C) /BT option -40°C ÷ +60°C (storage -20°C ÷ +70°C)
Ambient temperature -AE execution = -20°C ÷ +60°C (storage -20°C ÷ +70°C)
-AES execution = -20°C ÷ +60°C (storage -20°C ÷ +70°C)
Fluid Hydraulic mineral oil HL, HLP as per DIN 51524
Recommended viscosity 20÷100 mm
2
/s - max allowed range 15 ÷ 380 mm
2
/s
Fluid contamination class ISO 4406 class 20/18/15 NAS 1638 class 9, in line filters of 10 μm (β10 _>75 recommended)
Fluid temperature -20°C +60°C (standard seals) -20°C +80°C (/PE option) -40°C +60°C (/BT option)
Coil code DHZO-A* DKZOR-A*
Coil resistance R at 20°C 3 ÷ 3,3
Ω
2 ÷ 2,2
Ω
13 ÷ 13,4
Ω
3,8 ÷ 4,1
Ω
2,2 ÷ 2,4
Ω
12 ÷ 12,5
Ω
Max. solenoid current 2,2 A 2,75 A 1 A 2,6 A 3,25 A 1,2 A
Max. power
30 Watt for DHZO-A execution; 35 Watt for DKZOR-A execution; 50 Watt for -AE and -AES executions
Protection degree (CEI EN-60529)
IP65 for -A execution; IP67 for -AE and -AES, executions
Duty factor Continuous rating (ED=100%)
standard option /6 option /18 standard option /6 option /18
9 ANALOG INTEGRAL DRIVERS -AE - OPTIONS
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to the driver power supply.
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers
Reference input signal
- analog differential input with ±10 VDC nominal range (pin D, E), proportional to desired coil current
Monitor output signal
- analog output signal proportional to the actual valve’s coil current (1V monitor = 1A coil current)
Following options are available to adapt standard execution to special application requirements:
9.1 Option /I
It provides the 4÷20 mA current reference signal instead of the standard ±10 V
DC. Monitor output signal is still the standard ±10 VDC
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
9.2 Option /Q
It provides the possibility to enable or disable the valve functioning without cutting the power supply (the valve functioning is disabled but the driver cur-
rent output stage is still active). To enable the driver supply a 24V
DC on the enable input signal.
9.2 Possible combined option: /IQ
CURRENT
TO COIL S2
REGULATIONS AND SWITCHES
7 PIN - STANDARD
MAIN CONNECTOR
BIAS
SCALE
RAMPS
B2
B1
S2
S1
positive bias adjust
쩨
쩨
쩨
쩨
쩨
(driver view)
negative bias adjust (only for double solenoid valves)
positive scale adjust
negative scale adjust (only for double solenoid valves)
B1:
B2:
S1:
S2:
(remove the rear cover)
SW
10 ANALOG INTEGRAL DRIVERS -AE - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
Selector SW
Dither frequency
[Hz]
SW1 SW2 SW3 SW4
ON
ON
ON
ON ON
ON ON
ON ON ON
ON ON ON
ON ON ON
ON ON ON
ON ON ON ON
The dither frequency is factory pre-
set at 200 Hz and its regulation may
be adjusted after contact with Atos
technical department
100
130
160
200 (Standard)
230
270
300
380
430
470
500
(only for double
solenoid valves)
쩨
쩨
RU
RD
ramp for increasing reference signal
ramp for decreasing reference signal
RU:
RD:
dither frequency selector (see table beside)
SW:
ON
OFF
PIN SIGNAL
TECHNICAL SPECIFICATIONS
NOTES
A V+ Power supply 24 VDC for solenoid power stage and driver logic Input - power supply
B V0 Power supply 0 VDC for solenoid power stage and driver logic Gnd - power supply
C
(1)
AGND Ground - signal zero for MONITOR signal Gnd - analog signal
ENABLE Enable (24 VDC) or disable (0 VDC) the driver (for /Q option) Input - on/off signal
D INPUT+
Reference analog differential input: ±10 VDC maximum range (4 ÷ 20 mA for /I option)
Default setting for single solenoid valves: 0÷+10 V
DC
Default setting for double solenoid valves: ±10 VDC
Input - analog signal
E INPUT -
F MONITOR
Monitor analog output: ±5 V
DC
maximum range; 1 V = 1 A
Output - analog signal
G EARTH Internally connected to the driver housing
Note: (1) with /Q option ENABLE signal replaces AGND on pin C; MONITOR signal is referred to pin B.
A minimum time of 60ms to 160ms have be considered between the driver energizing with the 24 VDC power supply and when the valve is ready
to operate. During this time the current to the valve coils is switched to zero
10.1 7 PIN MAIN CONNECTOR
11 DIGITAL INTEGRAL DRIVERS -AES - OPTIONS
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to each driver power supply
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers.
Reference input signal
- analog differential input with ±10VDC nominal range (pin D,E), proportional to desired coil current (4÷20 mA with cable
break detection, ±10 mA, ±20 mA or 0÷20 mA software selectable)
Monitor output signal
- analog output signal proportional to the actual valve’s coil current (1V monitor = 1A coil current)
Following options are available to adapt standard execution to special application requirements:
11.1 Option /Q
To enable the driver, supply 24Vdc on pin C referred to pin B: when the enable signal is set to zero the valve status is software selectable, by factory
default the valve functioning is disabled (zero current to the solenoid) but the driver current output stage is still active. For the complete list of selectable
status, see tab. G115.
11.2 Option /Z
It provides, on the 12 pin main connector, the following additional features:
Logic power supply
Separated power supply for the solenoid (pin 1, 2) and for the digital electronic circuits (pin 9, 10).
Cutting solenoid power supply allows to interrupt the valve functioning but keeping energized the digital electronics thus avoiding fault conditions of the
machine fieldbus controller. This condition allows to realize safety systems in compliance with European Norms EN13849-1 (ex EN954-1).
Enable Input Signal
To enable the driver, supply 24Vdc on pin 3 referred to pin 2: when the enable signal is set to zero the valve status is software selectable, by factory
default the valve functioning is disabled (zero current to the solenoid) but the driver current output stage is still active. For the complete list of selectable
status, see tab. G115.
Fault Output Signal
Fault output signal indicates fault conditions of the driver (solenoid short circuits/not connected, reference signal cable broken for 4÷20mA input, etc.).
Fault presence corresponds to 0
VDC
, normal working corresponds to 24
VDC (pin 11 referred to pin 2)
: Fault status is not affected by the Enable input signal
11.3 Option /W - only for valves coupled with pressure compensator type HC-011 or KC-011 (see tab. D150).
It provides, on the 12 pin main connector, the above option /Z features plus the hydraulic power limitation function.
The driver receives the flow reference signal by the analog external input INPUT+ and a pressure transducer remotely installed in the hydraulic system,
has to be connected to the driver’s analog input TR.
When the actual requested hydraulic power pxQ (TR x INPUT+) reaches the max power limit (p1xQ1), internally set by software, the driver automatically
reduces the flow regulation of the valve. The higher is the pressure feedback the lower is the valve’s regulated flow:
Flow regulation = Min
(
PowerLimit [sw setting]
; Flow Reference [INPUT+]
)
Transducer Pressure [TR]
For detailed information on hydraulic power limitation, see tab. G115
F160
12 DIGITAL INTEGRAL DRIVERS -AES - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
COMMUNICATION CONNECTOR
12 PIN - OPTION /Z and /W
7 PIN - STANDARD
5 PIN
Serial (-PS)
5 PIN
Pressure
connection (/W)
5 PIN
PROFIBUS (-BP)
5 PIN
CANopen (-BC)
RAMPS
BIASSCALE
MAIN CONNECTOR
(driver view)
(driver view)
CURRENT
TO COIL S2
(for double
solenoid valves)
(driver view)
LINEARIZATION
(driver view)
(driver view)
For electronic connections of digital drivers
AEG and controllers AEZ, see tab. G120
12.1 7 or 12 PIN MAIN CONNECTOR (-AES standard, /Q, /Z, /W options)
Standard
7pin
/Z, /W options
12pin
SIGNAL TECHNICAL SPECIFICATIONS NOTES
A 1 V+
Power supply 24 VDC for solenoid power stage (and for driver logic on 7 pin connection)
Input - power supply
Gnd - power supply
B 2 V0 Power supply 0 VDC for solenoid power stage
(and for driver logic on 7 pin connection)
C
(option /Q)
3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver Input - on/off signal
D 4 INPUT+
Reference analog input: ±10 VDC / ±20 mA maximum range software selectable
Default setting for single solenoid valves: 0÷+10 V
DC, differential input
Default setting for double solenoid valves: ±10 V
DC, differential input
/Z and /W options: common mode INPUT+ referred to AGND
Input - analog signal
E - INPUT -
C 5 AGND Ground - signal zero for MONITOR signal (INPUT+ signal only for /Z and /W options) Gnd - analog signal
F 6 MONITOR Monitor analog output: ±5 VDC maximum range; Default setting 1V = 1A Output - analog signal
- 7 NC do not connect
- 8 MONITOR 2
2nd monitor analog output: ±5 VDC maximum range (only for /W option)
Output - analog signal
- 9 VL+ Power supply 24 VDC for driver logic
Input - power supply
Gnd - power supply
- 10 VL0 Power supply 0 VDC for driver logic
- 11 FAULT Fault (0 VDC) or normal working (24 VDC) Output - on/off signal
G PE EARTH Internally connected to the driver housing
Note: A minimum time of 270 to 340 ms have be considered between the driver energizing with the 24 VDC power supply and when the valve is ready to operate.
During this time the current to the valve coils is switched to zero.
15
SOFTWARE TOOLS
The driver configuration and parameters can be easily set with the Atos E-SW programming software, available in four different versions according to the
driver’s communication execution: E-SW-PS (Serial), E-SW-BC (CANopen), E-SW-BP (PROFIBUS DP), E-SW-EH (EtherCAT). Programming software
E-SW-BC, E-SW-BP, E-SW-EH for BC, BP and -EH drivers, can be also used to modify the valve’s parameterization through the serial communication inter-
face, without disconnecting the valve from the machine’s bus line.
For a more detailed description of software interface, PC requirements, adapters, cables and terminators, please refer to technical table G500.
Programming software, must be ordered separately:
E-SW-* (mandatory - first supply) = Dvd including E-SW-* software installer and operator manuals; it allows the registration to Atos digital service
E-SW-*-N (optional - next supplies) = as above but not allowing the registration to Atos digital service
On first supply of the E-SW-* software, it is required to apply for the registration in the Atos download area: www.download.atos.com.
Once the registration is completed, the password will be sent by email.
The software remains active for 10 days from the installation date and then it stops until the user inputs his password.
With the password you can also download, in your personal area, the latest releases of the Atos software, manuals, drivers and configuration files.
COMMUNICATION CONNECTOR
12 PIN - OPTION /Z and /W
7 PIN - STANDARD
RAMPS
BIASSCALE
MAIN CONNECTOR
(driver side)
(driver side)
LINEARIZATION
(driver side)
5 PIN
Serial (-PS)
4 PIN (input)
EtherCAT (-EH)
(driver side)
4 PIN (output)
EtherCAT (-EH)
(driver side)
DIGITAL INTEGRAL DRIVER -AES-EH - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
13
13.1 4 & 5 PIN M12 COMMUNICATION CONNECTORS
EtherCAT (-EH)
PIN SIGNAL TECHNICAL SPECIFICATION
1 TX+ Transmitter
2 RX+ Receiver
3 TX- Transmitter
4 RX- Receiver
Housing Shield Positioned on control cabinet side
Serial (-PS)
PIN SIGNAL TECHNICAL SPECIFICATION
1 NC do not connect
2 NC do not connect
3 RS_GND Signal zero data line
4 RS_RX Valves receiving data line
5 RS_TX Valves transmitting data line
5 PIN
Pressure
connection (/W)
(driver side)
12.2 ELECTRONIC CONNECTIONS - 5 PIN COMMUNICATION AND PRESSURE TRANSDUCER CONNECTORS
Serial (-PS) CANopen (-BC) PROFIBUS DP (-BP)
PIN SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION
1 NC do not connect CAN_SHLD Shield +5V for termination
2 NC do not connect NC do not connect LINE-A Bus line (high)
3 RS_GND Signal zero data line CAN_GND Signal zero data line DGND data line and termination Signal zero
4 RS_RX Valves receiving data line CAN_H Bus line (high) LINE-B Bus line (low)
5 RS_TX Valves transmitting data line CAN_L Bus line (low) SHIELD do not connect
PIN Input Voltage (Software selectable) Input Current (Software selectable)
1 VT Remote transducer power supply 24 VDC VT Remote transducer power supply 24 VDC
2 TR Remote transducer signal (0 ÷ 10 VDC) TR Remote transducer signal (0 ÷ 20 mA)
3 AGND signal zero for power supply and signal NC do not connect
4 NC do not connect NC do not connect
5 NC do not connect NC do not connect
12.3 5 PIN M12 PRESSURE CONNECTOR (only for /W option)
Note: for the electronic connections of 7 or 12 pin main connector, see section 12.1
for pressure transducer electronic connector (option /W) see section 12.3)
MODEL CODES OF POWER SUPPLY AND COMMUNICATION CONNECTORS (to be ordered separately)
14
666
connectors supplyed with the valve
VALVE VERSION
CONNECTOR CODE
ZH-7P ZM-7P ZH-12P ZH-5P ZH-5P/BP ZM-4PM/EH
PROTECTION DEGREE
IP65 IP67 IP67 IP67 IP67 IP67
-A -AE, -AES -AES/Z
-Serial (-PS)
or
CANopen (-BC)
PROFIBUS DP
(-BP)
IP67
EtherCAT (-EH)
DATA SHEET
K500 G110, G115, K500
G115, K500
ZH-5PM
IP67
-AES/W
-AEZ
G115, K500
Max flow Δp= 70bar
[l/min]
20 80 100
SPOOL TYPE
L1 L3 S3 L5 S5
40
S2
6
L14
16
DIAGRAMS FOR DHZO (based on mineral oil ISO VG 46 at 50 °C)
5.1 Regulation diagrams
1 = linear spool L14
2 = linear spool L1
3 = progressive spool S2
4 = linear spool L3
5 = progressive spool S3, D3
6 = linear spool L5
7 = progressive spool S5, D5
16.2 Flow /
Δ
p diagrams
stated at 100% of valve stroke
1 = spool L14
2 = spool L1
3 = spool S2
4 = spool S3, L3, D3
5 = spool S5, L5, D5
F160
Max flow [l/min] at
Δ
p = 30 bar
Max flow [l/min] at
Δ
p = 30 bar
Stroke [% of max] Stroke [% of max]
Reference signal [V]
X = Threshold for bias activation depending to the valve type and amplifier type
Reference signal [V]
2
5
6
3
4
16.4 Operation as throttle valve
Single solenoid valves (DHZO-*-051)
can be used as simple throttle valves:
Pmax = 250 bar (option /Y advisable)
Flow rate [l/min]
Valve pressure drop Δp [bar]
2
1
Valve pressure drop Δp [bar]
4
5
Note: hydraulic configuration vs reference signal for
double solenoid valves (standard and option /B)
Reference signal 0 ÷ +10 V
P 촞 A / B 촞 T
12 ÷ 20 mA
Reference signal 0 ÷ -10 V
P 촞 B / A 촞 T
4 ÷ 12 mA
Hydraulic configuration vs reference signal
for single solenoid valves:
Reference signal:
0 ÷ +10 V P 촞 A / B 촞 T (standard)
4 ÷ 20 mA P 촞 B / A 촞 T (option /B)
1
7
3
}
}
}
Valve pressure drop Δp [bar]
Flow rate [l/min]
16.3 Operating limits
1 = spool L14
2 = spool L1
3 = spool S2
4 = spool L3, S3, D3
5 = spool L5, S5, D5
2
1
4
3
5
Flow rate [l/min]
17
DIAGRAMS FOR DKZOR (based on mineral oil ISO VG 46 at 50 °C)
Max flow [l/min] at
Δ
P = 30 bar
Max flow [l/min] at
Δ
P = 30 bar
Stroke [% of max] Stroke [% of max]
1
2
4
3
17.4 Operation as throttle valve
Single solenoid valves (DKZOR-*-151)
can be used as simple throttle valves:
Pmax = 250 bar (option /Y advisable)
100 160
SPOOL TYPE
L3 S3 S5
Flow rate [l/min]Valve pressure drop
Δ
P [bar]
Flow rate [l/min]
1
2
2
1
17.1 Regulation diagrams
1 = linear spool L3
2 = progressive spool S3, D3
3 = linear spool L5
4 = progressive spool S5, D5
17.2 Flow /Δp diagrams
stated at 100% of valve stroke
1 = spool S3, L3, D3
2 = spool S5, L5, D5
17.3 Operating limits
1 = spool L3, S3, D3
2 = spool L5, S5, D5
Reference signal [V]
X = Threshold for bias activation depending to the valve type and amplifier type
Reference signal [V]
L5
Max flow Δp= 30 bar
[l/min]
Note:
Hydraulic configuration vs reference signal for
double solenoid valves (standard and option /B)
Reference signal 0 ÷ +10 V
P 촞 A / B 촞 T
12 ÷ 20 mA
Reference signal 0 ÷ -10 V
P 촞 B / A 촞 T
4 ÷ 12 mA
Hydraulic configuration vs reference signal
for single solenoid valves:
Reference signal:
0 ÷ +10 V P 촞 A / B 촞 T (standard)
4 ÷ 20 mA P 촞 B / A 촞 T (option /B)
}
}
}
Valve pressure drop Δp [bar]
18 INSTALLATION DIMENSIONS FOR DHZO [mm]
Mass: 3,1 kg
Mass: 3,1 kgMass: 2,3 kg
Mass: 2,3 kg
Mass: 1,9 kg
DHZO-A-05
DHZO-AES-05 DHZO-AES-07
DHZO-AE-05 DHZO-AE-07
ISO 4401: 2005
Mou
nting surface: 4401-03-02-0-05
(see table P005)
(for /Y version, surface 4401-03-03-0-05 without X port)
Fastening bolts: 4 socket head screws M5x50 class 12.9
Tightening torque = 8 Nm
Seals: 4 OR 108; 1 OR 2025
Diameter of ports A, B, P, T: Ø 7,5 mm (max)
Diameter of port Y: Ø = 3,2 mm (only for /Y option)
Note: for option /B the solenoid is at side of port A
Mass: 2,6 kg
V
F160
666
666
666
ZH-7P or ZM-7P
ZH-7P or ZM-7P
쩸
ZH-7P or ZM-7P
ZH-7P or ZM-7P
쩸
훾
훽
훿
훾
훽
훿
DHZO-A-07
Mass: 3,2 kg
Mass: 2,4 kg
DHZO-AES-EH-05 DHZO-AES-EH-07
쩸
ZH-7P or ZM-7P
ZH-7P or ZM-7P
쩸
훽
쩸
dotted line = 12 pin connector ZH-12P for option /Z, /W
-BP communication interface, ZH-5P/BP connector
-BC communication interface, ZH-5P connector
-PS communication interface, ZH-5P connector
훿
훾
-Option /W pressure transducer interface, ZH-5PM connector
-EH communication interface (input), ZM-4PM/EH connector
훽
-EH communication interface (output), ZM-4PM/EH connector
훽
19 INSTALLATION DIMENSIONS FOR DKZOR [mm]
ISO 4401: 2005
Mou
nting surface: 4401-05-04-0-05
(see table P005)
(for /Y version, surface 4401-05-05-0-05 without X port)
Fastening bolts: 4 socket head screws M6x40 class 12.9
Tightening torque = 15 Nm
Seals: 5 OR 2050; 1 OR 108
Diameter of ports A, B, P, T: Ø 11,2 mm (max)
Diameter of port Y: Ø = 5 mm (only for /Y option)
03/15
Mass: 5,0 kg
Mass: 5,0 kgMass: 4,3 kg
Mass: 4,3 kg
Mass: 3,8 kg
DKZOR-A-15
DKZOR-AES-15 DKZOR-AES-17
DKZOR-A-17
DKZOR-AE-15 DKZOR-AE-17
Mass: 4,5 kg
Note: for option /B the solenoid is at side of port A
V
666
666
666
ZH-7P or ZM-7P
ZH-7P or ZM-7P
쩸
ZH-7P or ZM-7P
쩸
ZH-7P or ZM-7P
훾
훽
훿
훾
훽
훿
Mass: 5,1 kgMass: 4,4 kg
DKZOR-AES-EH-15 DKZOR-AES-EH-17
쩸
ZH-7P or ZM-7P
쩸
ZH-7P or ZM-7P
훽
훽
쩸
dotted line = 12 pin connector ZH-12P for option /Z, /W
-BP communication interface, ZH-5P/BP connector
-BC communication interface, ZH-5P connector
-PS communication interface, ZH-5P connector
훿
훾
-Option /W pressure transducer interface, ZH-5PM connector
-EH communication interface (input), ZM-4PM/EH connector
훽
-EH communication interface (output), ZM-4PM/EH connector