www.suco.de
42
www.suco.de
42
www.suco.de
42
Pressure switches 30 A/F
Changeover switch
Technical data
Temperature stability
for diaphragm / seal materials:
NBR
EPDM
FKM
-40 °C – +100 °C
-30 °C – +120 °C
-5 °C – +120 °C
Switching frequency: 200 / min.
Mechanical life expectancy:
10
6
cycles (life expectancy of diaphragm pressure
switches only for pressures up to max. 50 bar)
Pressure rise rate: ≤ 1 bar/ms
Hysteresis:
Type 0159: approx. 10 – 30 % (not adjustable)
Type 0161, 0162, 0175: approx. 10 – 30 % (factory adjustable)
Vibration resistance: 10 g / 5 – 200 Hz sine-wave
Shock resistance: 294 m/s
2
; 14 ms half-sine-wave
Body material: Aluminium
Degree of protection: IP 65 socket device tted
Weight in grams:
Type 0159, 0161, 0162 approx. 240 g
Type 0175: approx. 310 g
Electrical Values 0159 0161/ 0162
Rated operating voltage U
e
: Rated operating current I
e
Application category
250 Volt AC 50 / 60 Hz 2.5 Ampere 5 Ampere AC 12
250 Volt AC 50 / 60 Hz 1 Ampere 1 Ampere AC 14
24 Volt DC 2 / 2 Ampere 3.5 / 3.5 Ampere DC 12 / DC 13
50 Volt DC 1 / 0.5 Ampere 2 / 1 Ampere DC 12 / DC 13
75 Volt DC 0.75 / 0.4 Ampere 1 / 0.5 Ampere DC 12 / DC 13
125 Volt DC 0.3 / 0.2 Ampere 0.3 / 0.2 Ampere DC 12 / DC 13
250 Volt DC 0.3 / 0.2 Ampere 0.25 / 0.2 Ampere DC 12 / DC 13
Rated insulation voltage U
i
: 300 V
Rated impulse withstand voltage U
imp
: 2.5 kV
Rated thermal current I
the
: 6 Ampere
Switching overvoltage: < 2.5 kV
Rated frequency: DC und 50 / 60 Hz
Short circuit current rating:
0159:
0161/0162:
To 2.5 Ampere
To 6.3 Ampere
Rated short-circuit current: < 350 Ampere
Tightening torque of terminal screws: < 0.35 Nm
Cross section: 0.5 – 1.5 mm
2
CE marking
SUCO pressure switches rated
with an operating limit of 250 V
are covered by the Low Voltage
Directive 73/23/EC.
An EC Declaration of Conformi-
ty has been issued for these
pressure switches and is on file
at our offices. The correspondi-
ng switches bear the CE mark
in our catalogue.
Mounting options
for wall or manifold
mounting enable easy,
free-maintenance
installation.
Easily user-adjustable
switching point.
High overpressure safety.
Socket device allows
easy assembly on site.
R o H S
compliant
www.suco.de
43
www.suco.de
43
www.suco.de
43
Aluminium body
With changeover switch and silver contacts
Overpressure safe to 200
/
600 bar
1)
Max. voltage 250 V
Switching point continuously adjustable by turning knurled screw while
in operation.
0159
Diaphragm / piston pressure switches 250 V
Pg 9
15
20
Ø 5.5
127
30
G1/4
p
max.
in bar
Adjustment
range in bar
Tolerance at
room temperature
Thread Order number:
0159 Diaphragm pressure switches
200
1)
0.2 – 2 ± 0.2 – 0.3
G 1⁄4 female
0159 426 14 X 001
0.5 – 5 ± 0.2 – 0.5 0159 427 14 X 001
1 – 10 ± 0.5 0159 428 14 X 001
2 – 20 ± 1.0 0159 429 14 X 001
5 – 50 ± 3.0 0159 430 14 X 001
10 – 100 ± 3.0 – 5.0 0159 431 14 X 001
0159 Piston pressure switches
600
1)
10 – 100 ± 3.0 – 5.0
G 1⁄4 female
0159 432 14 X 001
25 – 250 ± 5.0 – 7.0 0159 433 14 X 001
40 – 400 ± 5.0 – 9.0 0159 434 14 X 001
Diaphragm / seal material
– areas of application
NBR
Hydraulic / machine oil, heating oil, air, nitrogen etc.
1
EPDM
Brake uid, ozone, acetylene, hydrogen etc.
2
FKM
Hydraulic uids (HFA, HFB, HFD), petrol/gasoline etc.
3
Temperature ranges of diaphragm / seal materials see page 42
Order number:
0159 XXX 14 X 001
Degree of protection IP65
The type approval does not apply without restriction to all environmental conditions. It is the responsi-
bility of the user to check whether the electrical connection complies with regulations other than those
stated, and whether it can be used for special applications which could not be foreseen by us.
Warning !
When using oxygen, the relevant accident prevention regulations must be observed. In addition,
we recommend that a maximum operating pressure of 10 bar is not exceeded.
Piston pressure switches are only to a limited extent suitable for use with gases.
See explanation on page 9.
Our pressure switches are
also available with factory
pre-set switching points.
For further technical data
and electrical values see
page 42 .
With female thread
R o H S
compliant
1)
Static pressure, dynamic pressures should be 30 to 50% lower. These values refer to the hydraulic or pneu-
matic part of the pressure switch.
www.suco.de
4444
Aluminium body
With changeover switch and silver contacts
Overpressure safe to 200 / 600 bar
1)
With socket device similar to DIN EN 175301 (DIN 43650)
Adjustable hysteresis at works
0161/ 0162
Diaphragm / piston pressure switches 250 V
39
ø 5.5
G
1
/
4
20
30
Pg 9
1
To adjust the set point, loose the locknut and turn
the set screw with a screwdriver. Clock-wise screwing
increases the switching pressure. After adjusting, tighten
the locknut again.
0161 With female thread
0162 Manifold mounting
p
max.
in bar
Adjustment range
in bar
(tolerance at room
temperature)
dim. A
in mm
Female thread G 1/4 Manifold mounting
Diaphragm pressure switches 0161 0162
2)
200
1)
0.5 – 1 (± 0.2)
15
0161 436 14 X 001 0162 436 14 X 001
0.5 – 5 (± 0.2 – 0.5) 0161 437 14 X 001 0162 437 14 X 001
1 – 10 (± 0.5) 0161 438 14 X 001 0162 438 14 X 001
10 – 50 (± 3.0) 0161 439 14 X 001 0162 439 14 X 001
50 – 100 (± 3.0 – 5.0) 0161 440 14 X 001 0162 440 14 X 001
Piston pressure switches 0161 0162
2)
600
1)
100 – 400 (± 5.0 – 9.0) 19.5 0161 441 14 X 001 0162 441 14 X 001
Diaphragm / seal material
– areas of application
NBR Hydraulic / machine oil, heating oil, air, nitrogen etc.
1
EPDM Brake uid, ozone, acetylene, hydrogen etc.
2
FKM Hydraulic uids (HFA, HFB, HFD), petrol/gasoline etc.
3
See page 42 for temperature ranges of diaphragm materials
Order number:
016X XXX 14 X 001
2)
0162:
Scope of supply includes O-ring NBR 5x1.5mm
R o H S
compliant
1
Our pressure switches are
also available with factory
pre-set switching points.
For further technical data
and electrical values see
page 42.
Degree of protection IP65
The type approval does not apply without restriction to all environmental conditions. It is the responsi-
bility of the user to check whether the electrical connection complies with regulations other than those
stated, and whether it can be used for special applications which could not be foreseen by us.
Warning !
When using oxygen, the relevant accident prevention regulations must be observed. In addition,
we recommend that a maximum operating pressure of 10 bar is not exceeded.
Piston pressure switches are only to a limited extent suitable for use with gases.
See explanation on page 9.
1)
Static pressure, dynamic pressures should be 30 to 50% lower. These values refer to the hydraulic or pneu-
matic part of the pressure switch.
83
www.suco.de
45
Degree of protection IP65
The type approval does not apply without restriction to all environmental conditions. It is the responsi-
bility of the user to check whether the electrical connection complies with regulations other than those
stated, and whether it can be used for special applications which could not be foreseen by us.
Warning !
When using oxygen, the relevant accident prevention regulations must be observed. In addition,
we recommend that a maximum operating pressure of 10 bar is not exceeded.
1)
Static pressure, dynamic pressures should be 30 to 50% lower. These values refer to the hydraulic or pneu-
matic part of the pressure switch.
www.suco.de
45
0175
Diaphragm pressure switches 250 V
Aluminium body
With changeover switch and silver contacts
Overpressure safe to 25 bar
1)
With socket device similar to DIN EN 175301 (DIN 43650)
Adjustable hysteresis at works
With female thread
R o H S
compliant
p
max.
in bar
Adjustment
range in bar
Tolerance at
room temperature
Thread Order number:
0175 Diaphragm pressure switches
25
1)
0.1 – 1 ± 0.1 – 0.2 G 1⁄4 female 0175 435 14 X 001
Diaphragm material
– areas of application
NBR
Hydraulic / machine oil, heating oil, air, nitrogen etc.
1
EPDM
Brake uid, ozone, acetylene, hydrogen etc.
2
FKM
Hydraulic uids (HFA, HFB, HFD), petrol/gasoline etc.
3
See page 42 for temperature ranges of diaphragm materials
Order number:
0175 435 14 X 001
1
To adjust the set point,
loose the locknut and
turn the set screw with
a screwdriver.
Clock-wise screwing
increases the switching
pressure. After adjusting,
tighten the locknut again.
1
Our pressure switches are
also available with factory
pre-set switching points.
For further technical data
and electrical values see
page 42.
set screw
Holes shown 90°
from true plane
for O-ring ø 19 x 3.5