Pilot Operated Proportional DC Valve
Series D*1FE
3-71
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
Characteristics
NEW: A-regeneration D*1FER
The new series of pilot operated proportional valves
D*1FE is designed for high precision applications that
require a safe middle position of the main spool at power
down.
The pilot is a 3-position valve with an overlapped middle
position. This ensures that the main stage spring pushes
the spool into the middle position at power down without
an unintended jerk of the actuator.
The D*1FE series is available in 5 sizes:
D31FE NG10 (CETOP05)
D41FE NG16 (CETOP07)
D81FE NG25 (CETOP08) for port diam. up to 26 mm
D91FE NG25 (CETOP08) for port diam. up to 32 mm
D111FE NG32 (CETOP10)
The innovative integrated regenerative function in the
A-line (optional) allows new energy saving circuits with
differential cylinders. The hybrid version can switch be-
tween regenerative mode and standard mode at any time.
Technical features
High dynamics
High flow
Defined spool positioning at power-down
Onboard electronics
NEW: Energy saving A-regeneration optionally
integrated
NEW: Switchable hybrid version
Further literature about the opportunities of energy
savings and more functional details of the integrated
regeneration is available on request.
A B
P T
G G
a
b
a
b
A B
P T
G G
a
b
A B
P T
G G
a
A B
P
T
X Y
a
0
b
b
G
G
D41FE Standard Standard D*1FE
NEW: Hybrid D*1FEZ
D41FEE52 (Standard)
Pilot Operated Proportional DC Valve
Series D*1FE
3-72
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
Regenerative and Hybrid function
D*1FER and D*1FEZ
Q
Q
Regeneration
Pump
A B
T P
Regenerative valve D*1FER
Hybrid valve D*1FEZ
D*1FER (regenerative valve)
Cylinder extending
D*1FEZ (hybrid valve)
Cylinder extending Cylinder extending
in regenerative mode (high speed) in standard mode (high force)
Q
Q
Regeneration
Pump
A B
T P
Q
Pump
A B
T P
Flow rate in % of nominal flow
Size
1)
Spool
Port
A-T P-A P-B B-A (R-Valve) B-A (Hybrid) B-T (Hybrid)
D41FER/Z 31/32 100% 50% 100% 50% 40% 20%
D91FER/Z 31/32 100% 50% 100% 50% 50% 25%
D111FER/Z 31/32 on request
1)
D31FE: For size NG10 please refer solution with sandwich- and adaptor plates "H10-1666L / H10-1662 / A10-1664 / A10-1665L" in chapter 12.
Pilot Operated Proportional DC Valve
Series D*1FE
3-73
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
Ordering Code
Directional
control
valve
Spool
position
on power
down
Command
signal
2)
not for size code 8.
3)
for regenerative and hybrid function at code 3 (NG10) please refer to solutions
with sandwich and adaptor plates "H10-1666L / H10-1662 / A10-1664 / A10-
1665L" in chapter 12.
FunctionSize
Design
series
(not required
for ordering)
SealsFlow Valve
options
Hybrid
option
Code Valve options
0 6+PE acc. EN175201-804
5 11+PE acc. EN175201-804
7 6+PE + Enable
Code Size
3 NG10 / CETOP05
4 NG16 / CETOP07
8 NG25 / CETOP08
9
1)
NG25 / CETOP08
11 NG32 / CETOP10
NG06
pilot
Propor-
tional
control
High
response
Pilot
connec-
tions
1 )
for enlarged connections
Ø 32 mm
Code
Flow [l/min]
at Dp = 5bar per metering edge
D31 D41 D81 D91 D111
D 90
E 120
F 200
H 400 450
L 1000
Code Signal Function
B 0...±10V
0...+10V
P -> B
E 0...±20mA
0...+20mA
P -> B
K 0...±10V
0...+10V
P -> A
S 4...20mA
12...20mA
P -> A
Code Hybrid option
0
Standard for
spool code B, E, R
L
5)
Hybrid valve 24V
normaly closed for
spool code Z
Code Seals
N NBR
V FPM
H for HFC fluid
Code Inlet Drain
1 internal external
2 external external
4 internal internal
5 external internal
5)
see page "Regenerative and hybrid
function" (not for D31FE)
EF1D C
Standard
Code Spool type
overlap 10%
E01
E02
B31
Q
B
= Q
A
/2
B32
Q
B
= Q
A
/2
NEW: hybrid
function
3) 4)
Code Spool type
overlap 10%
Z31
Z32
NEW: regenerative
function
2) 3)
Code Spool type
overlap 10%
R31
R32
4)
nor for D31FE and D81FE
A B
PT
1
T
2
A B
PT
1
T
2
D31FE spooltype: R31 , R32 R61
A B
PT
1
T
2
Please order connector separately.
See chapter 3 accessories.
Pilot Operated Proportional DC Valve
Series D*1FE
3-74
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
General
Design Proportional directional control valve, pilot operated
Actuation VCD®-actuator
Size
NG10 (CETOP 05) NG16 (CETOP 07) NG25 (CETOP 08) NG32 (CETOP 10)
D31 D41 D81 / D91 D111
Mounting Interface DIN 24340 / ISO 4401 / CETOP RP121 / NFPA
Mounting position unrestricted
Ambient temperature [°C] -20...+60
MTTF
D
value [years] 50
Weight [kg] 11.3 14.2 23.5 64.5
Vibration resistance [g]
10 Sinus 5...2000 Hz acc. IEC 68-2-6
30 Random noise 20...2000 Hz acc. IEC 68-2-36
15 Shock acc. IEC 68-2-27
Hydraulic
Max. operating pressure [bar]
Internal Pilot Drain P, A, B, X 350; T, Y 35
External Pilot Drain P, A, B, T, X 350; Y 35
Fluid Hydraulic oil acc. DIN 51524...535, other on request
Fluid temperature [°C] -20...+60
Viscosity permitted [cSt] /
recommended [cSt] /
[mm2/s]
[mm2/s]
20...380
30...80
Filtration ISO 4406 (1999) 18/16/13 (meet NAS 1638: 7)
Nominal flow at Dp = 5 bar per control edge
1)
[l/min] 120 200 400/450 1000
Max. recommended Flow (Standard) [l/min] 250 600 1000 3000
Regenerative B-A / B-T depending on application, see flow curves
Leakage at 100 bar [ml/min] 200 200 600 1000
Pilot [ml/min] < 100
Pilot supply pressure [bar] 20...350
Pilot flow, during step response at 210 bar [l/min] 9 10 18 30
Static / Dynamic
Step response at 100% stroke
2)
[ms] 13 19 24 60
Frequency response
Amplitude ±5 % at 210 bar
Phase ±5 % at 210 bar
[Hz]
[Hz]
180
130
80
100
65
75
38
64
Hysteresis [%] < 0.1
Sensitivity [%] < 0.05
Temperature drift of Center Position [%/K] < 0.025
Electrical
Duty ratio [%] 100
Protection class IP65 in accordance with EN 60529 (with correctly mounted plug-in connector)
Supply voltage / ripple [V] 22...30, ripple < 5% eff., surge free
Current consumption max. [A] 3.5
Pre-fusing [A] 4.0 A medium lag
Input signal Code K (B) voltage
Impedance
[V]
[kOhm]
+10...0...-10, ripple < 0.01 % eff., surge free, 0...+10V P–>A (P–>B)
100
Code E voltage
Impedance
[mA]
[Ohm]
+20...0...-20, ripple < 0.01 % eff., surge free, 0...+20mA P–>B
250
Code S current
Impedance
[mA]
[Ohm]
4...12...20, ripple < 0.01 % eff., surge free, 12...20 mA P–>A
250
< 3.6 mA = enable off, > 3.8 mA = enable on acc. NAMUR NE43
Input Capacitance typ. [nF] 1
Differential input max. Code 0 [V] 30 for terminal D and E against PE (terminal G)
11 for terminal D and E against 0V (terminal B)
Code 5 [V]
30 for terminal 4 and 5 against PE (terminal W )
11 for terminal 4 and 5 against 0V (terminal 2)
Code 7 [V] 30 for terminal D and E against PE (terminal G)
Enable signal Code 5/7 [V] 5...30, Ri = 9 kOhm
Diagnostic signal [V] +10...0...-10 / +Ub, rated max. 5 mA
EMC EN 61000-6-2, EN 61000-6-4
Electrical connection Code 0/7 6 + PE acc. EN 175201-804
Code 5 11 + PE acc. EN 175201-804
Wiring min. Code 0/7 7 x 1.0 AWG16 overall braid shield
Code 5 8 x 1.0 AWG16 overall braid shield
Wiring lenght max. [m] 50
Technical Data
1)
Flow rate for different Dp per control edge:
2)
Measured with load (210 bar pressure drop/two control edges)
Q
x
= Q
Nom.
·
Dp
x
Dp
Nom.
Pilot Operated Proportional DC Valve
Series D*1FE
3-75
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
Wiring
Code 0, 6 + PE acc. EN 175201-804
Technical Data / Electronics
Code 5, 11 + PE acc. EN 175201-804
Code 7, 6 + PE acc. EN 175201-804 + enable
=
~
V
A
F
B
E
C
G
D
0
o
+
Power supply
24V
Command
0...±10V
0...±10V
4...20mA
0...±20mA
Diagnostics
valve stroke
=
~
V
0
o
+
Power supply
24V
Enable
Command
0...±10V
0...±10V
4...20mA
0...±20mA
o
+
5...30V
Diagnostics
valve stroke
4
5
3
6
10
2
11
9
7
1
8
Pin 3 and 8 internally connected
Pin 9 and 11 internally connected
Pin 10 n.c.
=
~
V
A
F
B
E
C
G
D
0
o
o
+
+
Power supply
24V
Enable
Command
0...±10V
0...±10V
4...20mA
0...±20mA
5...30V
Diagnostics
valve stroke
Duty ratio 100%
Protection class IP 65 in accordance with EN 60529 (with correctly mounted plug-in connector)
D41 D91 D111
Supply voltage [V] 24 24 24
Tolernace supply voltage [%] ±10 ±10 ±10
Current consumption [A] 1.21 0.96 1.29
Power consumption [W] 29 23 31
Solenoid connection Connector as per EN 175301-803
Wiring min. [mm²] 3 x 1.5 recommended
Wiring length max. [m] 50 recommended
With electrical connections the protective conductor (PE W) must be connected according to the relevant regulations.
Electrical characterisrics hybrid option
Pilot Operated Proportional DC Valve
Series D*1FE
3-76
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
D111FE on request
D81/91FE
Characteristic Curves
D41FE
All characteristic curves measured with HLP46 at 50°C.
P-A
B-T
P-B
A-T
-80
-60 -40 -20 0 20 40 60 80 100-100
75
50
25
50%
(B*)
B-TP-B
Command signal [%]
Flow [% of nominal flow]Q
P-B
A-T
P-A
B-T
-80
-60 -40 -20 0 20 40 60 80 100-100
75
50
25
0
50%
(B*)
B-TP-B
Command signal [%]
Flow [% of nominal flow]Q
P-A
B-T
P-B
A-T
-80
-60 -40 -20 0 20 40 60 80 100-100
75
50
25
0
50%
(B*)
B-TP-B
Command signal [%]
Flow [% of nominal flow]Q
-80
P-A
B-T
P-B
A-T
-60 -40 -20 0 20 40 60 80 100-100
75
50
25
0
50%
(B*)
B-TP-B
Command signal [%]
Flow [% of nominal flow]Q
Frequency response
±5% / ±25% / ±90% command signal
Dynamics at 210 bar pilot supply pressure
D31FE
D*1FEB/E flow curves
at Dp = 5 bar per metering edge
D31FE
spool type E01/02, B31/32
D41FE
spool type E01/02, B31/32
D111FE
Spool type E01/02, B31/32
D81/91FE
Spool type E01/02, B31/32
Pilot Operated Proportional DC Valve
Series D*1FE
3-77
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
All characteristic curves measured with HLP46 at 50°C.
D*1FER/Z flow curves
at Dp = 5 bar per metering edge
D31FE
spool type R31/32
D41FE
spool type R/Z31/32
D111FE
Spool type R/Z* on request
D91FE
Spool type R/Z31/32
Characteristic Curves
Pilot Operated Proportional DC Valve
Series D*1FE
3-78
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
1/16 NPTF
1/16 NPTF
P T
C
B
Y X
P
T
C
B
(drawn offset)
1/16"NPTF
1/16"NPTF
C
B
1/8”NPTF
M6 DIN906
T P
X P
(drawn offset)
1/16"NPTF
1/16"NPTF
X
B
C
Y
T
(drawn offset)
P
M6 DIN906
1/16 NPTF
T
C
B
(drawn offset)
P
B
C 1/16"NPTF
1/16"NPTF
X
(drawn offset)
internal
external
internal
external
external
external
internal
internal
open, closed
Pilot oil
Inlet
Drain
B C
B C
a
A B
P
Tx y
a
0
b
b
G
G
Pilot Flow
Pilot oil inlet (supply) and outlet (drain)
D31FEB/E D31FER
D41FEB/E D41FER D41FEZ
D81/91FEB/E D91FER D91FEZ
D111FEB/E D111FER D111FEZ
Pilot Operated Proportional DC Valve
Series D*1FE
3-79
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
251
92
108 315
164
44.5
Only function
code Z*
A B
Only function
code Z*
Dimensions
D31FE
D41FE
Surface finish
BK385
4x M6x40
DIN 912 12.9
13.2 Nm
±15%
NBR: SK-D31FP
FPM: SK-D31FP-V
Surface finish
BK320
2x M6x55
4x M6x60
DIN 912 12.9
13.2 Nm ±15%
63 Nm ±15%
NBR: SK-D41FP
FPM: SK-D41FP-V
238
70
122
283
31
A
B
B A
Regenerative and hybrid function with additional plate "H10-1666L / H10-1662 / A10-1664 / A10-1665L", see chapter 12.
Pilot Operated Proportional DC Valve
Series D*1FE
3-80
D_1FE UK.INDD RH 01.09.2011
Catalogue HY11-3500/UK
Parker Hannifin Corporation
Hydraulics Group
3
59
398 / 373 (Hybrid)
198
325
515
526
Only function
code Z*
A B
Only function
code Z*
274
116
384
230
57
A B
Only function
code Z*
Only function
code Z*
Dimensions
D111FE
D81/91FE
Surface finish
BK360
6x M12x75
DIN 912 12.9
108 Nm
±15%
NBR: SK-D81/D91FP
FPM: SK-D81/D91FP-V
Surface finish
BK386
6x M20x90
DIN 912 12.9
517 Nm
±15%
NBR: SK-D111FP
FPM: SK-D111FP-V