EN 18.145.3/03.24
1
Pressure Transmitter
HPT 1400
IO-Link interface
EX-Applications, Hydrogen
EX-Applications, Hydrogen
EX-Applications, Hydrogen
EX-Applications, Hydrogen
Relative pressure
Device t
emperature
Accuracy 0.5 %
Description
Features
IO-Link interface
Further switching output or
analogue output (0.. 10 V or 4 ..
20mA) as an option
Robust
Small and compact design
Device temperature monitoring
Description
The HPT 1400 with IO-Link interface is a digital pressure transmitter that has
been specially designed for series use in extremely small spaces. As most of
our pressure transmitters, HPT 1400 is based on a robust and long-life thin-
film sensor.
All of the parts in contact with the fluid (sensor and pressure connection) are
made of stainless steel and are welded together. This means, there are no
sealing points inside of the sensor. Leakage can therefore be excluded.
A basic accuracy of ≤±0.5 %FS typical for HPT 1400, combined with low
temperature drift open up a wide range of applications for HPT 1400.
Fields of application
Wide field of applications in the mechanical engineering sector, such as:
-Hydraulics
-Pneumatics
-Cooler unit
-Compressor
-and much more
2
EN 18.145.3/03.24
Technical data
Input data AB C
Measurement ranges bar 16 25 40 60 100 250 400 600
Overload pressures bar 32 50 80 120 200 500 800 1000
Burst pressure bar 125 125 200 300 500 1250 2000 2000
Mechanical connection G 1/4 A ISO 1179-2, external thread
Tightening torque, recommended 20 Nm
Parts in contact with fluid Connector: Stainless steel
Seal: FKM
Output data
Output signal IO-Link V1.1
Additional switching output or analogue output as an option
Switching output PNP Transistor switching output
(parameterisable: PNP, NPN or Push-Pull)
Further optional Push-Pull transistor switching output
Switching current: max. 250 mA per switching output
Analogue output, permitted load 4 .. 20 mA, R
Lmax
= U
B
– 8V / 20 mA [kΩ], load max. 500 Ω
0 .. 10 V, R
Lmin
= 2 kΩ,
Accuracy
1)
acc. to DIN 16086,
Terminal based
2)
≤ ± 0.5 % FS typ.
≤ ± 1.0 % FS max.
Accuracy
2)
acc. to minimum value setting
(B.F.S.L.)
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
Temperature compensation zero point ≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Temperature compensation span ≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Rise time ≤ 5 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Environmental conditions / Approvals / Tests
Compensated temperature range -25 .. +85 °C
Operating temperature range
3)
-40 .. +100 °C / -25 .. +100 °C
Storage temperature range -40 .. +100 °C
Fluid temperature range
3)
-40 .. +125 °C / -25 .. +125 °C
EMC DIN EN 61000-6-1/ 2/ 3/ 4
Vibration resistance DIN EN 60068-2-6 ≤ 25 g (10 .. 500 Hz)
Shock resistance DIN EN 60068-2-27 100 g / 6 ms / half sine
500 g / 1 ms / half sine
Protection type
4)
DIN EN 60529 IP 67
/ conformity
Provided
approval
Provided
Other data
Supply voltage
when applied acc. to UL specifications
9 .. 35 V DC, if PIN 2 = SP2
18 .. 35 V DC, if PIN 2 = Analogue output
(each 18 .. 30 V DC for communication operation)
- limited energy – acc. to 9.3 UL 61010; Class 2;
UL 1310 / 1585; LPS UL 60950
Residual ripple of supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 10 million load cycles (0 .. 100 % FS)
Weight ~ 45 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit protection are provided.
FS (Full Scale) = relative to complete measuring range
B.F.S.L. = Best Fit Straight Line
1) The accuracy indications refer to the –measured value (process value or ISDU Index 112, Subindex 1).
2) Including non-linearity, hysteresis, offset and final value deviation
3) In the standard up to -25 °C with FKM seal, -40 °C on request
4) With mounted mating connector in corresponding protection type
EN 18.145.3/03.24
3
IO-Link specific data
IO-Link revision V1.1
Transmission rate, Baud rate 38.4 kbit/s (COM2)
Minimus Cycle Time 2.5 ms
Process data width 16 bit
SIO Mode supported Yes
Sensor profile GPS
M-Sequence capability PREOPERATE = TYPE_1_V (8 Byte)
OPERATE = TYPE_2_2
ISDU supported
Download of the IO Device Description (IODD) at:
https://ioddfinder.io-link.com/#/
Pin connections
M12x1, 4 pole Pin
Output signal: F31
Signal Description
Q2/QA/n.c.
1 L+ +U
B
2 Q2/QA/n.c. Switching output 2 or
analogue output or
n.c.
3 L- 0 V
4 Q1/C Switching output 1 /
IO-Link communication
Dimensions
Orifice
Model code
Mechanical connection
Electrical connection
6 = Plug connector M12x1, 4 pole (without mating connector)
Output signal
F31 = IO-Link
Pressure ranges in bar
0016; 0025; 0040; 0060; 0100; 0160; 0250; 0400; 0600
Modification number
000 = Standard
4 = G1/4 A ISO 1179-2 with orifice
HPT 1 4
4 6
-
F31
-
( - X )
XXXX
-
000
Appropriate accessories, such as mating connectors for the electrical connection, can be found in the Accessories brochure.
Accessories:
(Optional:
F31 - 1 = IO-Link interface + 1 additional Push-Pull transistor switching output
F31 - B = IO-Link interface + analogue output 0 .. 10 V, 3 conductor
F31 - C = IO-Link interface + analogue output 4 .. 20 mA, 3 conductor)
4
EN 18.145.3/03.24
Note
The information in this brochure relates to the operating condi-
tions and applications described.
For applications and/or operating conditions not described please
contact the relevant technical department.
Subject to technical modifications.
HYDAC ELECTRONIC GMBH
Hauptstrasse 27
D-66128 Saarbruecken
Phone: +49 (0)6897 509-1
Fax: +49 (0)6897 509-1726
Email: electronic@hydac.com
Website: www.hydac.com