171
EN 18.365.3/02.18
2
Description:
EDS 8000 is an electronic pressure switch
in compact design which is simple to adjust.
Models with one or two transistor outputs (PNP
or NPN) are available.
The switch points are set using the two keys
and a four-digit display. During operation the
switching position is indicated by either a red
or a green backlight in the display.
For optimum adaptation to a particular
application, the instrument has many
additional adjustment parameters, e.g.
switching delay times, N/O / N/C function of
the outputs.
EDS 8000 is available in various pressure
ranges between 0 .. 25 bar and 0 .. 600 bar.
The main applications of the EDS 8000 are
to indicate pressures and limits in hydraulics
and pneumatics, or any application where
high switching frequency or constant
switching accuracy would overburden a
mechanical pressure switch.
Technical data:
Input data
Measuring ranges bar 25 40 100 250 400 600
Overload pressures bar 80 80 200 500 800 1000
Burst pressure bar 200 200 500 1000 2000 2000
Mechanical connection G1/4 A ISO 1179-2
Tightening torque, recommended 20 Nm
Parts in contact with fl uid Mech. connection: Stainless steel
Seal: FKM
Output data
Switching outputs 1 or 2 transistor outputs PNP or NPN
Switching current: max. 250 mA per output
Switching cycles: > 100 million
Accuracy acc. to DIN 16086,
terminal based
≤ ± 0.5 % FS typ.
≤ ± 1 % FS max.
Temperature compensation, zero point ≤ ± 0.02 % FS / °C typ.
≤ ± 0.03 % FS / °C max.
Temperature compensation, span ≤ ± 0.02 % FS / °C typ.
≤ ± 0.03 % FS / °C max.
Repeatability ≤ ± 0.5 % FS max.
Reaction time < 10 ms
Long-term drift ≤ ± 0.25 % FS max. / year
Environmental conditions
Compensated temperature range -25 .. +85 °C
Operating temperature range
1)
-40 .. +100 °C / -25 .. +100 °C
Nominal temperature range of display (read-out) -15 .. + 70 °C
Storage temperature range -40 .. 85 °C
Fluid temperature range
1)
-40 .. +125 °C / -25 .. +125 °C
mark
EN 61000-6-1 / 2 / 3 / 4
mark
2)
Certi cate no.: E318391
Vibration resistance acc. to
DIN EN 60068-2-6 (0 .. 500 Hz)
approx. 10 g
Shock resistance acc. to
DIN EN 60068-2-27 (11 ms)
approx. 50 g
Protection class acc. to DIN EN 60529
3)
IP 67
Other data ≤ 5 %
Supply voltage
when applied acc. to UL speci cations
9.6 .. 32 V DC
- limited energy - acc. to 9.3 UL 61010; Class 2;
UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage
Current consumption max. 0.535 A total
max. 35 mA (with inactive switching output)
Display 4-digit, LED, 7-segment,
height of digits 4.5 mm
Weight ~ 70 g
Note: Reverse polarity protection of the supply voltage, overvoltage, override and short circuit
protection are provided.
FS (Full Scale) = relative to complete measuring range
1)
-25 °C with FKM seal, -40 °C on request
2)
Environmental conditions acc. to 1.4.2 UL 61010-1; C22.2 No 61010-1
3)
With mounted mating connector in corresponding protection class
Up to 2 switching outputs
Pressure Switch
EDS 8000
Relative pressure Display
172
EN 18.365.3/02.18
2
Model code:
EDS 8 4 4 6 - X - XXXX – X00
Mechanical connection
4 = G 1/4 A ISO 1179-2
Electrical connection
6 = male M12x1, 4 pole
(mating connector not supplied)
Output
1 = 1 switching output
2 = 2 switching outputs
Measuring ranges in bar
0025; 0040; 0100; 0250; 0400; 0600
Modication number
000 = standard
N00 = version with NPN switching outputs
Accessories:
Appropriate accessories, such as mating connectors and mechanical adapters, can be found in
the Accessories brochure.
Setting options:
All the terms and symbols used for setting
the EDS 8000 as well as menu structure
comply with the specications of the
German Engineering Federation Standard
(VDMA 24574-1) for pressure switches.
The
EDS 8000 is easy and convenient to set up using
the two buttons.
Setting ranges for the
switching outputs:
Measuring
range
in bar
Lower limit of
RP / FL
in bar
Upper limit of
SP / FH
in bar
0 ..
25
0.25 25.00
0 ..
40
0.4 40.0
0 .. 100
1.0 100.0
0 .. 250
2.5 250.0
0 .. 400
4 400
0 .. 600
6 600
Measuring
range
in bar
Min. difference
betw. RP and SP
& FL and FH
Incre-
ment*
in bar
0 .. 25 0.25 0.05
0 .. 40 0.4 0.1
0 .. 100 1.0 0.2
0 .. 250 2.5 0.5
0 .. 400 4 1
0 .. 600 6 1
* All ranges given in the table can be adjusted
by the increments shown.
SP = switch point
RP = switch-back point
FL = pressure window lower value
FH = pressure window upper value
Additional functions:
Switching mode of the switching outputs
adjustable (switch point function or window
function)
Switching direction of the switching outputs
adjustable (N/C or N/O function)
Switch-on and switch-off delay adjustable
from 0.00 .. 99.99 seconds
Display lter for smoothing the display value
during pressure pulsations
Pressure can be displayed in
bar, psi, MPa
Pin connections:
Dimensions:
M12x1, 4 pole
Pin EDS 8446-1 EDS 8446-2
1 +U
B
+U
B
2 n.c. SP2
3 0 V 0 V
4 SP1 SP1
Male connector M12x1 4 pole
HYDAC ELECTRONIC GMBH
Hauptstr. 27, 66128 Saarbrücken
Germany
Telephone +49 (0)6897 509-01
Fax +49 (0)6897 509-1726
e-mail: electronic@hydac.com
Internet: www.hydac.com
Note:
The information in this brochure relates to the
operating conditions and applications described.
For applications or operating conditions not
described, please contact the relevant technical
department.
Subject to technical modications.