EN 18.056.7/02.18
153
2
Pressure Switch
EDS 300
Relative pressure Display
Description:
The EDS 300 is a compact, electronic
pressure switch with integrated digital display.
The integrated pressure sensor is based on a
measurement cell with thin- lm strain gauge
on a stainless steel membrane.
Four different output models are available:
with one switch point or with two switch points
and both models can also have an additional
analogue output signal 4 .. 20 mA.
The switch points and the associated
hystereses can be adjusted using the key
pad. For optimum adaptation to a particular
application, the instrument has many
additional adjustment parameters, e.g.
switching delay times, N/O / N/C function of
the outputs.
The main applications of the EDS 300 are
to indicate pressures and limits in hydraulics
and pneumatics and anywhere where high
switching frequency or constant switching
accuracy would overburden a mechanical
pressure switch.
Technical data:
Input data
Measuring ranges bar 16 40 100 250 400 600
Overload pressures bar 32 80 200 500 800 1000
Burst pressure bar 200 200 500 1000 2000 2000
Mechanical connection G1/4 A ISO 1179-2
Tightening torque, recommended 20 Nm
Parts in contact with fl uid Mech. connection: Stainless steel
Seal: FKM
Output data
Switching outputs 1 or 2 PNP transistor outputs
Switching current: max. 1.2 A per
switching output
Switching cycles: > 100 million
Analogue output, permitted load resistance 4 .. 20 mA load resist. max. 400 Ω
Accuracy acc. to DIN 16086,
terminal based
≤ ± 0.5 % FS typ.
≤ ± 1 % FS max.
Temperature compensation, zero point ≤ ± 0.02 % FS / °C typ.
≤ ± 0.03 % FS / °C max.
Temperature compensation, span ≤ ± 0.02 % FS / °C typ.
≤ ± 0.03 % FS / °C max.
Repeatability ≤ ± 0.5 % FS max.
Reaction time approx. 10 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Environmental conditions
Compensated temperature range -10 .. +70 °C
Operating temperature range -25 .. +80 °C
Storage temperature range -40 .. +80 °C
Fluid temperature range -25 .. +80 °C
mark
EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to
DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 10 g
Shock resistance acc. to
DIN EN 60068-2-27 (11 ms)
≤ 50 g
Protection class acc. to DIN EN 60529
1)
IP 65
Other data
Supply voltage 20 .. 32 V DC
Residual ripple of supply voltage ≤ 5 %
Current consumption approx. 100 mA (inactive switching output)
Display 3-digit, LED, 7 segment, red,
height of digits 9.2 mm
Weight ~ 300 g
Note: Reverse polarity protection of the supply voltage, overvoltage, override and short circuit
protection are provided.
FS (Full Scale) = relative to complete measuring range
1)
With mounted mating connector in corresponding protection class
Up to 2 switching outputs
Analogue output