81 311/118 ED
3/8
PRE*
SERIES 20
7 - INSTALLATION
We recommend installing the PRE* valve either in horizontal
position, or vertical position with the solenoid downward. If the valve
is installed in vertical position and with the solenoid upward, you
must consider possible variations of the minimum controlled
pressure, if compared to what is indicated in paragraph 2.
Ensure there is no air in the hydraulic circuit. In particular
applications, it can be necessary to vent the air entrapped inside
the solenoid tube, by using the apposite drain screw (see par. 8 - 9
- 10). At the end of the operation, make sure of having correctly
screwed the drain screw.
Connect the T port on the valve directly to the tank. Add any
backpressure value detected in the T line to the controlled pressure
value.
Maximum admissible backpressure in the T line, under
operational conditions, is 2 bar.
Valves are fixed by means of screws or tie rods on a flat surface
with planarity and roughness equal to or better than those indicated
in the relative symbols. If minimum values are not observed, fluid
can easily leak between the valve and support surface.
Surface finishing
5 - ELECTRICAL CHARACTERISTICS
Proportional solenoid
The proportional solenoid comprises two parts: tube and coil.
The tube, screwed to the valve body, contains the armature which is
designed to maintain friction to a minimum thereby reducing
hysteresis.
The coil is mounted on the tube secured by means of a lock nut and
can be rotated through 360° depending on installation clearances.
6 - STEP RESPONSE
(obtained with mineral oil with viscosity of 36 cSt at 50°C and electronic
control card)
Step response is the time taken for the valve to reach 90% of the
set pressure value following a step change of reference signal.
The table illustrates typical step response times measured with a
PRE32-210 and with input flow rate Q = 50 l/min, and a pressure oil
volume of 2 litres. The response time is affected by both the flow
rate and the oil volume inside the piping.
REFERENCE SIGNAL STEP 0 → 100% 100 → 0%
Step response [ms] 120 90
NOMINAL VOLTAGE
V DC
12 24
RESISTANCE (at 20°C)
Ω 3.66 17.6
NOMINAL CURRENT
A 1.88 0.86
DUTY CYCLE
100%
ELECTROMAGNETIC
COMPATIBILITY (EMC)
According to
2014/30/EU
CLASSOFPROTECTION
atmospheric agents (IEC 60529)
coil insulation (VDE 0580)
impregnation
IP 65
class H
class F
3
- MAX PRESSURE VALUES
This valve incorporates a mechanical limit of the maximum pressure, that operates independently of the applied current. This kind of design
ensures the pressure cannot rise over even if the solenoid current exceeds the maximum current (I > I
m
ax
).
Values obtained with oil viscosity of 36 cSt at 50°C, Q = 50 l/min
4 - HYDRAULIC FLUIDS
Use mineral oil-based hydraulic fluids HL or HM type, according to ISO 6743-4. For these fluids, use NBR seals (code N). For fluids HFDR type
(phosphate esters) use FPM seals (code V). For the use of other kinds of fluid such as HFA, HFB, HFC, please consult our technical
department.
Using fluids at temperatures higher than 80 °C causes a faster degradation of the fluid and of the seals characteristics. The fluid must be
preserved in its physical and chemical characteristics.
PRE*-025 PRE*-070 PRE*-140 PRE*-210 PRE*-350
pressure value at 800 mA (bar) 27 85 147 220 365
max pressure value when I > I
max
(bar) 35 95 165 255 370