41 270/121 ED
1/12
0.75
30.2
40.5
21.5
5.1
12.7
31.75
BA
T
P
M5
15.5
25.9
31
Ø7.5 (max)
41 270/121 ED
M*F3(M)
SHUT-OFF VALVES
SOLENOID OR HYDRAULICALLY
ACTUATED, WITH OR WITHOUT
POSITION MONITORING
SERIES 10
MOUNTING INTERFACE OPERATING PRINCIPLE
M*F3 are shut-off valves, solenoid or hydraulically
actuated, with or without spool position monitoring, in
modular version, with mounting interface according to
ISO 4401-03 standard.
M*F3 valves are placed under directional control
servovalves in order to guarantee the safety of circuit
when a power failure occurs.
Spools with float, closed, parallel or cross position in de-
energized condition are available.
— Versions with spool monitoring do not have
manual override and can not be disass-
embled, because of their characteristics and
their possible use on machinery subject to
safety requirements.
The spool position monitoring is available
either for initial position or for actuated
position.
PERFORMANCE RATINGS
(working with mineral oil of viscosity of 36 cSt at 50°C)
ISO 4401-03-02-0-05
(CETOP 4.2-4-03-350)
MODULAR VERSION
ISO 4401-03
p max 350 bar
Q max 50 l/min
MDF3 MCF3
Maximum operating pressure:
P - A - B ports
T port
bar
350
210
350
25
Pilot pressure:
min
max
bar
-
15 (NOTE)
210
Maximum flow rate l/min
50 40
Ambient temperature range °C
-20 / +50
Fluid temperature range °C
-20 / +80
Fluid viscosity range cSt
10 ÷ 400
Fluid contamination degree
According to ISO 4406:1999
class 20/18/15
Recommended viscosity cSt
25
Mass kg
1,5 1,3
NOTE: The pilot pressure must be 10 to
20 bar higher than the return pressure to
allow the fluid discharge from the
pressure chamber.
41 270/121 ED
2/12
M*F3
SERIES 10
1 - IDENTIFICATION CODES
1.1 - M*F3 valves
Directional valve,
modular version
Actuation:
D = solenoid
C = hydraulically
Side of the control element:
A = side A (not available for FC fail safe position)
B = side B (not available for FP fail safe position)
Fail Safe feature
ISO 4401-03 size
Power supply (omit for MCF3 valves):
D12 = 12 V
D24 = 24 V
D48 = 48 V
D110 = 110 V
D220 = 220 V
D00 = valve without coils (see NOTE 1)
Fail safe position:
F1 = closed (working ports closed)
F3 = float (working ports connected to a return line)
FP = parallel (P1→A1, B1→T1)
FC = cross (P→B1, A1→T)
Seals:
N = NBR seals for mineral oil (standard)
V = FPM seals for special fluids
Series:
(the overall and mounting dimensions remain
unchanged from 10 to 19)
M F 3
-
/
10
-
K1
Side of the control element:
A = side A (not available for FC fail safe position)
B = side B (not available for FP fail safe position)
Fail safe position:
F1 = closed (working ports closed)
FP = parallel (P1→A1, B1→T1)
FC = cross (P→B1, A1→T)
Coil electrical connection
(omit for MCF3 valves):
plug for connector type EN 175301-803
(ex DIN 43650)
NOTE: The locking ring of the coil and the relevant O-Rings are supplied together with valves.
Directional valve,
modular version
Actuation:
D = solenoid
C = hydraulically
Fail Safe feature
ISO 4401-03 size
Power supply (omit for MCF3M valves):
D12 = 12 V
D24 = 24 V
D48 = 48 V
D110 = 110 V
D220 = 220 V
D00 = valve without coils (see NOTE 1)
Spool position monitoring
Seals:
N = NBR seals for mineral oil (standard)
V = FPM seals for special fluids
Series:
(the overall and mounting dimensions remain
unchanged from 10 to 19)
M F 3
M
-
/
10
-
K1
Coil electrical connection
(omit for MCF3M valves):
plug for connector type EN 175301-803
(ex DIN 43650)
NOTE: The locking ring of the coil and the relevant O-Rings are supplied together with valves.
Monitored position:
(see par. 14 for switching logic)
MA = monitored position ‘a’
MB = monitored position ‘b’
1.2 - M*F3M valves with monitored spools
41 270/121 ED
3/12
M*F3
SERIES 10
2 - HYDRAULIC SYMBOLS
2.1 - MDF3 valves
NOTE: P1, T1, A1, B1
are plate side.
NOTE: P1, T1, A1, B1
are plate side.
2.2 - MCF3 valves
F1A F1B
closed fail safe position
F3A F3B
float fail safe position
F1A F1B
closed fail safe position
F3A F3B
float fail safe position
FPA FCB
parallel fail safe position cross fail safe position
FPA FCB
parallel fail safe position cross fail safe position
41 270/121 ED
4/12
M*F3
SERIES 10
2.3 - MDF3M valves with monitored spools
2.4 - MCF3M valves
Type F1B:
1 solenoid side B - closed fail safe position
Sensor MA Sensor MB
Type FPA:
1 solenoid side A - parallel fail safe position
Sensor MA Sensor MB
Type FCB:
1 solenoid side B - cross fail safe position
Sensor MA Sensor MB
Type FPA:
hydraulic actuation side A - parallel fail safe position
Sensor MA Sensor MB
Type FCB:
hydraulic actuation side B - cross fail safe position
Sensor MA Sensor MB
NOTE: P1, T1, A1, B1 are plate side.
NOTE: P1, T1, A1, B1 are plate side.
5 - OPERATING LIMITS
The values have been obtained according to ISO 6403 norm with solenoids at rated temperature and supplied with voltage equal to 90% of the
nominal voltage. The values have been obtained with mineral oil, viscosity 36 cSt, temperature 50 °C and filtration according to ISO 4406:1999
class 18/16/13.
41 270/121 ED
5/12
M*F3
SERIES 10
4 - PRESSURE DROPS Δp-Q
(obtained with viscosity 36 cSt at 50 °C)
6 - SWITCHING TIMES
The values indicated are obtained according to ISO 6403 standard,
with mineral oil viscosity 36 cSt at 50°C.
TIMES [ms] ENERGIZING DE-ENERGIZING
MDF3 - F1 60 ÷ 90 20 ÷ 50 ms
SPOOL
TYPE
De-energizing Energizing
with flow
in A and B
without flow
in A and B
CURVES ON GRAPH
F1*, F3* 1 2 1
FCB 4 3 3
SPOOL
TYPE
De-actuating Actuating
pilot pressure
tank +10 bar
pilot pressure
tank +20 bar
CURVES ON GRAPH
FCB 1 3 2
MD*3-F1*, MD*3-F3*
MDF3-*
MCF3-*
M*F3-FCB
3 - HYDRAULIC FLUIDS
Use mineral oil-based hydraulic fluids HL or HM type, according to ISO 6743-4. For these fluids, use NBR seals (code N). For fluids HFDR type
(phosphate esters) use FPM seals (code V). For the use of other fluid types such as HFA, HFB, HFC, please consult our technical department.
Using fluids at temperatures higher than 80 °C causes a faster degradation of the fluid and of the seals characteristics. The fluid must be
preserved in its physical and chemical characteristics.
41 270/121 ED
6/12
M*F3
SERIES 10
7 - MDF3 - ELECTRICAL FEATURES
7.1 - Solenoids
These are essentially made up of two parts: tube and coil. The tube
is threaded into the valve body and includes the armature that
moves immersed in oil, without wear. The inner part, in contact with
the oil in the return line, ensures heat dissipation.
The coil is fastened to the tube by a threaded ring; versions without
the spool monitoring and can be rotated, to suit the available space.
NOTE 1: In order to further reduce the emissions, use of type H
connectors is recommended. These prevent voltage peaks on
opening of the coil supply electrical circuit (see cat. 49 000).
NOTE 2: The IP65 protection degree is guaranteed only with the
connector correctly connected and installed.
7.2 - Current and absorbed power
The table shows current and power consumption values relevant to
the different coil types for DC.
Using connectors type "D" (see cat. 49 000) with embedded bridge
rectifier it is possible to feed DC coils (starting from 48V voltage)
with alternating current (50 or 60 Hz), considering a reduction of the
operating limits of about 5-10%.
VOLTAGE SUPPLY FLUCTUATION
± 10% Vnom
MAX SWITCH ON FREQUENCY
18.000 ins/hr
DUTY CYCLE
100%
ELECTROMAGNETIC COMPATIBILITY
(EMC) (NOTE 1)
In compliance with
2014/30/EU
LOW VOLTAGE
In compliance with
2014/35/EU
CLASS OF PROTECTION
Atmospheric agents (IEC 60529)
Coil insulation (VDE 0580)
Impregnation
IP65 (NOTE 2)
class H
class F
Coils for direct current (values ±10%)
Nominal
voltage
[V]
Resistance
at 20°C
[Ω]
Current
consumpt.
[A]
Power
consumpt
[W]
Coil
code
D12 12 4,4 2,72 32,7 1903080
D24 24 18,6 1,29 31 1903081
D48 48 78,6 0,61 29,5 1903083
D110 110 423 0,26 28,2 1903464
D220 220 1692 0,13 28,2 1903465
8 - ELECTRIC CONNECTORS
Solenoid operated valves are delivered without connectors. Connectors can be ordered separately. See catalogue 49 000.
9 - MDF3 OVERALL AND MOUNTING DIMENSIONS
dimensions in mm
1
Mounting surface with sealing rings:
4 OR type 2037 (9.25x1.78) - 90 Shore
2
Standard manual override included in the
solenoid tube
3 Coil 360° revolving
4 Coil removal space
5
EN 175301-803 (ex DIN 43650) electrical
connector to be ordered separately
(see cat. 49 000)
6 Connector removal space
MDF3-F1*
MDF3-F3*
41 270/121 ED
7/12
M*F3
SERIES 10
dimensioni in mm
MDF3-FPA
MDF3-FCB
1
Mounting surface with sealing rings:
4 OR type 2037 (9.25x1.78) - 90 Shore
2
Standard manual override included in the
solenoid tube
3 Coil 360° revolving
4 Coil removal space
5
EN 175301-803 (ex DIN 43650) electrical
connector to be ordered separately
(see cat. 49 000)
6 Connector removal space
41 270/121 ED
8/12
M*F3
SERIES 10
10 - MCF3 OVERALL AND MOUNTING DIMENSIONS
dimensions in mm
MCF3-F1*
MCF3-F3*
MCF3-FCB
MCF3-FPA
1 Mounting surface with sealing rings:
4 OR type 2037 (9.25x1.78) - 90 Shore
2 1/4” BSP connection for hydraulic
actuation
3 Hexagon: spanner 38
Tightening torque 35 ÷ 40 Nm
41 270/121 ED
9/12
M*F3
SERIES 10
11 - MDF3M OVERALL AND MOUNTING DIMENSIONS
dimensions in mm
MDF3M - FPA
1
Mounting surface with sealing rings:
4 OR type 2037 (9.25x1.78) - 90 Shore
2
Coil
3
Position sensor: setting sealed at factory,
do not tamper.
4
Connector for position sensor.
To be ordered separately (see cat. 41 505)
5
EN 175301-803 (ex DIN 43650) electrical
connector to be ordered separately
(see cat. 49 000)
6
Connector removal space
MDF3M - FCB
41 270/121 ED
10/12
M*F3
SERIES 10
MDF3M - F1B
dimensions in mm
1
Mounting surface with sealing rings:
4 OR type 2037 (9.25x1.78) - 90 Shore
2
Coil
3
Position sensor: setting sealed at factory,
do not tamper.
4
Connector for position sensor.
To be ordered separately (see cat. 41 505)
5
EN 175301-803 (ex DIN 43650) electrical
connector to be ordered separately
(see cat. 49 000)
6
Connector removal space
41 270/121 ED
11/12
M*F3
SERIES 10
12 - MCF3M OVERALL AND MOUNTING DIMENSIONS
MCF3M - FPA
dimensions in mm
1
Mounting surface with sealing rings:
4 OR type 2037 (9.25x1.78) - 90 Shore
2 1/4” BSP connection for hydraulic actuation
3
Position sensor: setting sealed at factory,
do not tamper.
4
Connector for position sensor.
To be ordered separately (see cat. 41 505)
5
EN 175301-803 (ex DIN 43650) electrical
connector to be ordered separately
(see cat. 49 000)
MCF3M - FCB
41 270/121 ED
12/12
M*F3
SERIES 10
REPRODUCTION IS FORBIDDEN. THE COMPANY RESERVES THE RIGHT TO APPLY ANY MODIFICATIONS.
13 - M*F3M POSITION SENSOR
WARNING ! Valve disassembling is not allowed.
Sensors must not be unscrewed or tampered.
Operating voltage range V DC 20 ÷ 32
Absorbed current A 0.4
Max output load mA 400
Output 2 PNP
Electric protections
polarity inversion
short circuit
Hysteresis mm ≤ 0.1
Operating temperature range °C - 25 / +80
Class of protection from
atmospheric agents (IEC 60529)
IP65
EMC
Electromagnetic compatibility
In compliance with
2014/30/EU
CONNECTION SCHEME
Pin Values Function
1
+24 V Supply
2
NC Normal Closed
3
0 V -
4
NO Normal Open
14 - SWITCHING LOGICS
14.1 - MA monitoring
Energized position monitored.
for M*F3M-*F*A valves
De-energized position monitored.
for M*F3M-F*B valves
14.2 - MB monitoring
De-energized position monitored.
for M*F3M-*A valves
Energized position monitored.
for M*F3M-*B valves