Diagnostics log (continued)
Fault
ID
Fault Description SPN FMI Severity SPN + FMI byte values as
seen in DM1/DM2 frames
Byte 3 Byte 4 Byte 5
14 Safety demodulator A: signal out of
range
Actuator component fault. 299009 2 SEVERE 0x01 0x90 0x82
16 Safety-controller PSU out of range Actuator component fault. 299010 2 SEVERE 0x02 0x90 0x82
18 Safety-controller fuse bit fault Actuator component fault. 299011 2 SEVERE 0x03 0x90 0x82
15 Safety demodulator B: signal out of
range
Actuator component fault. 299012 2 SEVERE 0x04 0x90 0x82
17 Safety-controller: Voltage reference
out of range
Actuator component fault. 299013 2 SEVERE 0x05 0x90 0x82
19 Safety-controller spool position
cross validation fault
Actuator component fault. 299014 2 SEVERE 0x06 0x90 0x82
20 Safety switch state fault Actuator component fault. Not able
to perform safe operation!
299015 12 SEVERE 0x07 0x90 0x8C
51 SPI buffer overload Actuator component fault. 299020 2 INFO 0x0C 0x90 0x82
52 SPI communication fault Actuator component fault. 299021 2 SEVERE 0x0D 0x90 0x82
25 Handshake bootup fault. Actuator component fault. 299022 12 SEVERE 0x0E 0x90 0x8C
26 Safety switch state fault. Actuator component fault. 299023 12 SEVERE 0x0F 0x90 0x8C
31 Spool position cross validation fault Actuator component fault. 299025 2 SEVERE 0x11 0x90 0x82
28 Safety-controler initialization fault. Actuator component fault. 299026 12 WARNING 0x12 0x90 0x8C
30 Safety-controller task scheduling
fault
Actuator component fault. 299028 12 SEVERE 0x14 0x90 0x8C
38 Memory (EEPROM) corrupted Actuator component fault. 299029 12 SEVERE 0x15 0x90 0x8C
64 CRC fault The Operator has not approved the
data change
299030 2 SEVERE 0x16 0x90 0x82
65 Invalid hardware version. Actuator component fault. 520448 2 SEVERE 0x00 0xF1 0xE2
56 AVEF from Work Function actuators
not recieved within timeout period
Auxillary Valve Estimated Flow not
recived from Work Function
actuators by Inlet actuator before
timeout specified
520449 19 WARNING 0x01 0xF1 0xF3
55 Corrupted data received by Inlet
actuator
CRC or DLC data received from Inlet
actuator is corrupted
520450 19 CRITICAL 0x02 0xF1 0xF3
54 COMM : Running number validation
for AVC and AVEF
The running number for Auxillary
Valve Command nd Auxillary Valve
Estimated Flow could not be
validated.
520451 19 CRITICAL 0x03 0xF1 0xF3
41 Memory (EEPROM) CRC fault Actuator component fault. 520576 2 INFO 0x80 0xF1 0xE2
37 PWM calibration Actuator component fault. 520577 2 SEVERE 0x81 0xF1 0xE2
40 Config sector CRC fault Actuator component fault. 520578 2 SEVERE 0x82 0xF1 0xE2
33 Memory (EEPROM) invalid
parameter
One or more configured EEPROM
parameters out of specified range.
520579 2 SEVERE 0x83 0xF1 0xE2
43 Average operating temp above
limit.
The average detected operating
temperature is above the upper
limit specified.
520580 16 WARNING 0x84 0xF1 0xF0
44 Current temp above upper limit. The current temperature the
actuator operates in is above
specified operation limit.
520581 0 CRITICAL 0x85 0xF1 0xE0
6 5V PSU out of range Actuator component fault. 520582 2 SEVERE 0x86 0xF1 0xE2
7 Spool position calculation fault Actuator component fault. 520583 2 SEVERE 0x87 0xF1 0xE2
50 LVDT supply frequency out-of-range Actuator component fault. 520584 2 SEVERE 0x88 0xF1 0xE2
8 V reference signal out of range. Actuator component fault. 520585 2 SEVERE 0x89 0xF1 0xE2
Technical Information
PVED-CC Series 5 ISObus
Diagnostics
30 |
©
Danfoss | October 2021 BC187186484889en-000107