InIn
Out NO
Out NC
Out NO
Out NC
Danfoss
93Z19.11
Input
Normally closed (NC)
Normally open (NO)
Connected to enclosure
of pressure control
-10 – 30 3 80 2 061B820166 1221-1A02000 061B810166 1231-1A02000 – – –
20 – 60 3 130 2 – – 061B810266 1431-1A02000 – – –
20 – 60 3 130 – – – – 75 061B800266 1411-1A00075
50 – 100 4 200 2 061B820366 2221-1A02000 061B810366 2231-1A02000 – – –
50 – 100 4 200 – – – 75 061B800366 2211-1A00075
70 – 120 5 220 2 – – 061B810466 2431-1A02000 – – –
70 - 120 5 220 – – – – – 75 061B800466 2411-1A00075
60 - 150 6 250 2 061B820566 2621-1A02000 061B810566 2631-1A02000 – – –
60 - 150 6 250 – – – – – 75 061B800566 2611-1A00075
Data sheet | Thermostat, MBC 8000 and MBC 8100
2 | 520B7816 | IC.PD.P10.D8.02
*) If higher vibrations are present in the system/installation, temperature controls with capillary tube or
armoured capillary tube are recommended.
Umgebungsbedingungen
Ambient temperature - 40 – 70 °C
Shock resistance:
50 g/6 ms
Acc. to EN 60068-2-27
Free fall acc. to EN 60068-2-32
Vibration resistance Sin 4 g, 5Hz – 200 Hz acc. to EN 60068-2-6. *
)
Enclosure
IP65 to EN 60529
Anodized AlMgSi 1, AW-6082 T6
Driftsbetingelser
Ambient temperature - 40 – 70 °C
Shock resistance:
50 g/6 ms
Acc. to EN 60068-2-27
Free fall acc. to EN 60068-2-32
Vibration resistance Sin 4 g, 5Hz – 200 Hz acc. to EN 60068-2-6. *
)
Enclosure
IP65 to EN 60529
Anodized AlMgSi 1, AW-6082 T6
Environmental conditions
Ambient temperature - 40 – 70 °C
Shock resistance
50 g/6 ms
Acc. to EN 60068-2-27
Free fall acc. to EN 60068-2-32
Vibration resistance Sin 4 g, 5Hz – 200 Hz acc. to EN 60068-2-6. *)
Enclosure
IP65 to EN 60529
Anodized AlMgSi 1, AW-6082 T6
Mechanical characteristics
Electrical connection DIN 43650 plug, Pg 9, Pg 11, Pg 13.5
Technical data
Electrical specications
Contact load (Alternating current)
0.5 A, 250 V, AC15
12 W, 125V, DC 13
Switch SPDT
Standard types
Setting
range
Fixed
di.
Max.
sensor
temp.
Cap.
tube
length
Capillary tube Armoured capillary tube Sensor
pocket
Rigid sensor
[°C] [°C] [°C] [m] Code no.
Type
MBC 8100
Code no.
Type
MBC 8100
[mm] Code no.
Type
MBC 8100
Input
Normally closed (NC)
Normally open (NO)
Connected to enclosure
of pressure control
© Danfoss | DCS (jmn) | 2017.02