TM1
Subject to change · TM1_9212_2en_02/2020
www.argo-hytos.com
Page 1
Temperature switch with two switching outputs
› Temperature switch with two adjustable switch points
› Simple switching point setting by means of two setting rings allowing optimum reading
› Mechanical locking prevents inadvertent switching point manipulation
› Particularly good response dynamics and very short power-on delay time
› Installation length 250 mm
› High vibration and shock resistance
› Certification acc. to EU direction
Technical Features
Temperature switch with the measuring thermistor Pt 1000 and two adjustable temperature switching points. Two adjusting rings are provided with scale
and their position is protected with a mechanical lock. The stainless-steel body is provided with connecting thread G 1/2 with FKM sealing ring. The needed
installation length for the measuring stem is 250 mm. An electric connection is realized by four-pin connector M12 x 1. The temperature switch is suitable for
industrial usage thanks to robust design, vibration and shock resisted.
Outputs: two switching contacts (pin 2 and pin 4)
Application
Measuring element 1x Pt 1000 (DIN EN 60751, class A)
Measuring range °C (°F) -25 … +140 (-13 … +284)
Set point SP °C (°F) -20 … + 140 (-4 … +284)
Media Liquids
Medium temperature °C (°F) -40 … +145 (-40 ... +293)
Ambient temperature °C (°F)
-40 … +80 (-40 ... +176) at medium temperature < 80 °C (+176 °F)
-40 … +50 (-40 ... +122) at medium temperature < 145 °C (+293 °F)
Storage temperature °C (°F) -40 … +100 (-40 ... +212)
Pressure rating bar (PSI) 300 (4350)
Electrical parameters
Supply voltage V DC 9.6 … 32 (supply class 2 acc. to cULus)
Current consumption mA < 30
Protection class III
IP protection IP67
Protection Reverse polarity protection
Power-on delay time s 0.5
Outputs
Two digital outputs Switching signals; PNP switcher (contacts normally open / closed)
Max. voltage drop switching output DC V 2
Permanent current rating of switching output DC mA 500
Electric protection Pulsed short-circuit and overload protection
Accuracy / deviations
Temperature drift per 10 K K 0.1
Repeatability K ± 0.1
Setting accuracy K ± 3
Response times
Dynamic response T05/T09 s 1/3; acc. to DIN EN 60751
Adjusting
Adjustment of the switching point Two setting rings with a mechanical lock
Tests / approvals
EMC
DIN EN 61000-4-2 ESD 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated 10 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-6 HF conducted 10 V
Shock resistance DIN IEC 68-2-27 50 g (11 ms)
Vibration resistance DIN IEC 60068-2-6 20 g (10 ….2000 Hz)