51 Return to Table of Contents V20.1
Proportional Flow Control Valve Specifications (Continued)
The digital amplifier controls all the functions for the whole proportional flow control valve
assembly. The transducer sends a signal to the digital amplifier that tells the digital amplifier how
far open the proportional flow control valve is in relation to the servo-proportional valve. The digital
amplifier will then control how much farther the proportional flow control valve will open. The
settings for the digital amplifier are set at Almo so that it is ready for operation when the valve
arrives.
Voltage Reference Signal – E0 Option
For this option, all you need to provide is a 0-10-volt command, which is proportionate to the
position of the valve. No additional amplifier card is needed. The valve requires a 24-volt supply
with a minimal electrical current of 3 amps per valve. It also must have a minimum pilot pressure of
40 psi. If the voltage or pressure drops below the minimum requirement, the valve shifts closed to
safe mode. There is more information about this option on the next page.
Current Reference Signal – E1 Option
You will need to provide a 4-20 mA command, for this option, which is proportionate to the
position of the valve. No additional amplifier card is needed. The valve must have a 24-volt supply
with a minimum electrical current of 4 mA per valve. It also requires a minimum pilot pressure of
40 psi. The valve will shift closed (safe mode) if the voltage or pressure drops below the minimum
requirement. The next page has more information about this option.
Repeatability 0.1%
Hysteresis 0.2%