MAIN CHARACTERISTICS - based on mineral oil ISO VG 46 at 50 °C
Note:
Above performance data refer to valves coupled with Atos electronic drivers,
see section
7
.
(1) with step reference input 0÷100% (2) with pilot pressure = 140 bar, see datailed diagrams in section 8.2
Ports P, A, T = 350 X = 350 Y 울 10
Ports P, A, T = 420 X = 350 Y 울 10
£ 0,1
min: 40% of system pressure max 350 recommended 140 ÷ 160
± 0,1
zero point displacement < 1% at DT = 40°C
Size
Max pressure [bar]
LIQZO
LIQZP
Nominal flow of pilot valve at Dp = 70 bar
[l/min]
Leakage of pilot valve at P = 100 bar [l/min]
Piloting pressure [bar]
Piloting volume [cm
3
]
Piloting flow (1) [l/min]
Response time 0
÷ 100% step signal (2) [ms]
Hysteresis [% of the max regulation]
Repeatability [% of the max regulation]
Thermal drift
Max regulated flow [l/min]
at Dp = 5 bar
at Dp = 10 bar
Max permissible flow
185
260
500
2,16
6,5
21
25
330
470
850
7,2
20
22
32
420
590
1050
8,9
25
22
40
780
1100
2000
17,7
43
25
50
1250
1750
3100
33,8
68
30
63
2100
3000
5000
42,7
76
34
80
4
0,2
8
0,2
28
0,5
40
0,7
100
0,7
100
0,7
W
ARNING
4
FIELDBUS - only for LES
Fieldbus allows the direct communication of the proportional valve with machine control unit for digital reference signal, diagnostics and
settings of functional parameters. Analog reference signal remain available on the main connector for quick commissioning and maintenance.
F
or detailed information about fieldbus features and specification see tech table GS510.
The loss of the pilot pressure causes the undefined position of the main spool.
T
he sudden interruption of the power supply during the valve operation causes the immediate main spool opening A n T or P n A (for
o
ption /A). This could cause pressure surges in the hydraulic system or uncontrolled movements which may lead to machine damages.
WARNING
T
o avoid overheating and possible damage of the electronic driver, the valves must be never energized without
h
ydraulic supply to the pilot stage. In case of prolonged pauses of the valve operation during the machine cycle, it is always advisable
to disable the driver (option /Q or /Z). A safety fuse 2,5 A installed on 24V
DC power supply of each valve is always recommended, see
a
lso Power supply note at sections
9
LIQZO-LEB, LES and LIQZP-LEB, LES proportional cartridges are CE marked according to the applicable Directives (e.g. Immunity/Emission
E
MC Directive and Low Voltage Directive). Installation, wirings and start-up procedures must be performed according to the general prescrip-
t
ions shown in table F003 and in the installation notes supplied with relevant components. The electrical signals of the valve (e.g. monitor
signals) must not be directly used to activate safety functions or components, as prescribed by the European standards (Safety requirements of
f
luid technology systems and components-hydraulics, EN-982).
2
G
ENERAL NOTES
Dp P-A or A-T
S
* options add the closed loop control of pressure (SP) or force (SL) to the basic functions of proportional directional valves flow regulation.
A dedicated algorithm alternates pressure (force) depending on the actual hydraulic system conditions.
An additional connector is available for transducers to be interfaced to the valve’s driver (1 pressure transducer for SP or 1 load cell for SL).
M
ain 12 pin connector is the same as /Z option plus two analog signals specific for the pressure (force) control.
For detailed information and connector wiring of options SP, SL see tech table GS212.
3
A
L
T
E
R
N
A
T
E
D
P
/
Q
C
O
N
T
R
O
L
S
-
o
n
l
y
f
o
r
L
E
S
Assembly position Any position
Subplate surface finishing Roughness index, Ra 0,4 flatness ratio 0,01/100 (ISO 1101)
MTTFd values according to EN ISO 13849 75 years, see technical table P007
Ambient temperature range
standard = -20°C ÷ +60°C /BT option = -40°C ÷ +60°C
Storage temperature range
standard = -20°C ÷ +70°C /BT option = -40°C ÷ +70°C
Coil resistance R at 20°C
3 ÷ 3,3 W
Max. solenoid current 2,6 A
Max. power 50 Watt
Insulation class
H (180°) Due to the occuring surface temperatures of the solenoid coils, the European standards
ISO 13732-1 and EN982 must be taken into account
Protection degree to DIN EN60529 IP66/67 with mating connector
Tropicalization Tropical coating on electronics PCB
Duty factor Continuous rating (ED=100%)
EMC, climate and mechanical load See technical table G004
Communication interface
USB
Atos ASCII coding
CANopen
EN50325-4 + DS408
PROFIBUS DP
EN50170-2/IEC61158
EtherCAT, POWERLINK
EtherNet/IP, PROFINET IO RT/IRT
IEC 61158
Communication physical layer
not insulated
USB 2.0 + USB OTG
optical insulated
CAN ISO11898
optical insulated
RS485
Fast Ethernet, insulated
100 Base TX