LIQZO-TE are 2-way proportional cartridge
valves, designed for mounting in manifold
blocks which provide proportional not
compensated flow control according to the
electronic reference signal.
They operate in association with electronic
drivers, see section
, which supply the
proportional valves with proper current to
align valve regulation to the reference
signal supplied to the electronic driver.
They are available in different executions:
-T, with position transducer
;
-TE, -TES as -T plus analogue (TE) or
digital (TES) integral electronics
.
The regulation is operated by means of a
poppet
with double piloting area, sli-
ding into a sleeve
l
and provided of inte-
gral LVDT position transducer .
The poppet is controlled in closed loop by
means of a proportional directional valve
type DHZO, see table F160.
The integral electronics
ensures factory
presetting, fine functionality plus valve-to-
valve interchangeability and simplified
wiring and installation.
The electronic main connector
is fully
interchangeable for -TE and -TES
executions.
Standard 7 pin main connector is used for
power supply, analog input reference and
monitor signals.
12 pin connector is used for option /Z.
Following communication interfaces are
available for the digital -TES execution:
-PS, Serial communication interface for
configuration, monitoring and firmware
updating through Atos PC software
• -BC, CANopen interface
• -BP, PROFIBUS-DP interface
The valves with -BC and -BP interfaces
can be integrated into a fieldbus
communication network and thus digitally
operated by the machine control unit.
Typical applications: plastic injection and
blow moulding, foundry and steel plants.
Mounting surface: ISO 7368
Sizes from 16 to 50
Max flow up to 2000 l/min with differential
pressure Δp
l=l5 bar, see section
.
Max pressure = 350 bar.
LIQZO
Flow control valve
T = with position transducer
TE = as T plus integral analog
electronics
TES = as T plus integral
digital electronics
Spool type (regulating characteristics):
L4 = linear
Series number
2***TES PS--- /*
1 MODEL CODE
25 L4 /
Electronics options, for -TE execution
see section
:
I = current reference input and monitor
(4÷20 mA)
F =fault signal
Q = enable signal
Z =enable, fault and monitor signals
(12 pin connector)
Electronics options, for -TES execution
see section
:
I = current reference input and monitor
(4÷20 mA)
Z =
double power supply, enable fault and
monitor signals (12 pin connector)
LIQZO-TES-PS-402L4
Proportional throttle cartridges type LIQZO-TES, 2-way
with position transducer, ISO 7368 sizes from 16 to 50
F320
Communication interfaces (only for TES)
PS = Serial
BC = CANopen
BP = PROFIBUS DP
Versions with reduced flow are available on request *2L2.
Integral electronics
Communication connector
Main connector
External pilot port
Poppet
Sleeve
Main stage position transducer
Pilot valve
2 ELECTRONIC DRIVERS
Valve model
Data sheet
Drivers model E-ME-T
G140
-T
E-RI-TE
G200
-TE
E-RI-TES
G210
-TES
Note: For power supply and communication connector see section 15
Seals material:
omit for NBR (mineral
oil & water glycol)
PE = FPM
250
350
600
22
1,58
3
HYDRAULIC CHARACTERISTICS (based on mineral oil ISO VG 46 at 50 °C)
Model
Size
Max pressure [bar]
Nominal flow of pilot valve at Δp = 70 bar [l/min]
Leakage of pilot valve at P = 100 bar [l/min]
Response time 0 ÷ 100% step signal [ms]
Piloting volume [cm
3
]
Hysteresis [% of the max flow]
Repeatability [% of the max flow]
Thermal drift
Max regulated flow [l/min]
at Δp = 5 bar
at Δp =10 bar
Max permissible flow
16
500
700
1200
25
2,16
25
800
1100
1800
30
7,0
32
1200
1700
2500
32
9,4
40
2000
2800
4000
40
17,7
50
350
15
1
0,5%
±
0,5%
LIQZO-T*
Hydraulic symbols
LIQZO-T LIQZO-TE, LIQZO-TES
Notes:
Above performance data refer to valves coupled with Atos electronic drivers,
see section
.
Recommended piloting pressure is 140 ÷ 160 bar.
In case of long time shutdown of the hydraulic supply to the pilot valve, the driver has to be switched off to avoid its overheating.
zero point displacement < 1% at ΔT = 40°C
LIQZO-T* proportional valves are CE marked according to the applicable Directives (e.g. Immunity/Emission EMC Directive and Low Voltage Directive).
Installation, wirings and start-up procedures must be performed according to the general prescriptions shown in table F003 and in the installation notes
supplied with relevant components.
The electrical signals of the valve (e.g. monitor signals) must not be directly used to activate safety functions, like to switch-ON/OFF the machine’s safety
components, as prescribed by the European standards (Safety requirements of fluid technology systems and components-hydraulics, EN-982).
4
GENERAL NOTES
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to the driver power supply
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers
Reference input signal
- analog differential input with ±10 VDC nominal range (pin D,E), proportional to desired valve spool position
Monitor output signal
- analog output signal proportional to the actual valve’s spool position with ±10 VDC nominal range
Following options are available to adapt standard execution to special application requirements:
6.1 Option /F
It provides a Fault output signal in place of the Monitor output signal, to indicate fault conditions of the driver (cable interruption of spool transducers or
reference signal - for /I option): Fault presence corresponds to 0 V
DC, normal working corresponds to 24 VDC
6.2 Option /I
It provides the 4÷20 mA current reference and monitor signals instead of the standard ±10 V
DC
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
6.3 Option /Q
It provides the possibility to enable or disable the valve functioning without cutting the power supply (the valve functioning is disabled but the driver cur-
rent output stage is still active). To enable the driver supply a 24V
DC on the enable input signal.
6.4 Option /Z
This option includes /F and /Q features, plus the Monitor output signal.
When the driver is disabled (
0 VDC
on Enable signal) Fault output is forced to 0
VDC
.
6.5 Possible combined options: /FI and /IZ
6 ANALOG INTEGRAL DRIVERS -TE - OPTIONS
Signal description
PIN
POSITION TRANSDUCER CONNECTOR SP-345
OUTPUT SIGNAL
SUPPLY -15 V
DC
SUPPLY +15 VDC
GND
1
2
3
4
SIZES 16 ÷ 40
1
2
3
4
5
CONNECTIONS FOR -T EXECUTION
Signal description
SUPPLY
SUPPLY
GND
PIN
1
2
3
SOLENOID POWER SUPPLY CONNECTOR SP-666
1
2
3
Signal description
PIN
POSITION TRANSDUCER CONNECTOR ZBE 06
OUTPUT SIGNAL
SUPPLY +24 V
DC
GND
NC
1
2
3
4
SIZE 50
4
2
3
1
8 DIGITAL INTEGRAL DRIVERS -TES - OPTIONS
7 ANALOG INTEGRAL DRIVERS -TE - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
12 PIN - OPTION /Z
REGULATIONS AND LED
7 PIN - STANDARD
MAIN CONNECTOR
BIAS
SCALE
DIAGNOSTIC
Standard
7pin
/Z option
12pin
SIGNAL
TECHNICAL SPECIFICATIONS
NOTES
A 1 V+ Power supply 24 VDC for solenoid power stage and driver logic
Input - power supply
Gnd - power supply
B 2 V0 Power supply 0 VDC for solenoid power stage and driver logic
C
(1)
7 AGND Ground - signal zero for MONITOR signal (for standard, /Z option) Gnd - analog signal
3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver (for /Q and /Z options) Input - on/off signal
D 4 INPUT+
Reference analog differential input: 0
÷
+10 V
DC
maximum range (4 ÷ 20 mA for /I option)
Input - analog signal
E 5 INPUT -
F
(2)
6 MONITOR Monitor analog output: ±10 VDC maximum range (4 ÷ 20 mA for /I option) Output - analog signal
11 FAULT Fault (0V) or normal working (24V) (for /F and /Z options) Output - on/off signal
- 8 R_ENABLE Repeat Enable - output repetition of Enable input Output - on/off signal
- 9 NC do not connect
Output - on/off signal
Output - on/off signal
- 10 NC
do not connect
G PE EARTH Internally connected to the driver housing
Notes:
(1) with /Q option ENABLE signal replaces AGND on pin C; MONITOR signal is reffered to pin B
(2) with /F option FAULT signal replaces MONITOR on pin F.
A minimum time of 50ms to 100ms have be considered between the driver energizing with the 24 V
DC
power supply and when the valve is ready to operate.
During this time the current to the valve coils is switched to zero.
B2
B1
S2
S1
positive bias adjust
LED:
LED
(driver view)
(driver view)
7.1 ELECTRONIC CONNECTIONS - 7 & 12 PIN MAIN CONNECTORS
not working
positive scale adjust
not working
OFF normal working; ON fault presence
B1:
B2:
S1:
S2:
(remove the rear cover)
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to each driver power supply
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers
Reference input signal
- analog differential input with ±10VDC nominal range (pin D,E), proportional to desired valve spool position
Monitor output signal
- analog output signal proportional to the actual valve’s spool position with ±10VDC nominal range
Following options are available to adapt standard execution to special application requirements:
8.1 Option /I
It provides 4÷20 mA current reference and monitor signals instead of the standard ±10 V.
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
8.2 Option /Z
It provides on the 12 pin main connector the following additional features:
Logic power supply
Separated power supply for the solenoid (pin 1, 2) and for the digital electronic circuits (pin 9, 10).
Cutting solenoid power supply allows to interrupt the valve functioning but keeping energized the digital electronics thus avoiding fault conditions of the
machine fieldbus controller. This condition allows to realize safety systems in compliance with European Norms EN13849-1 (ex EN954-1).
Enable Input Signal
To enable the driver, supply 24V
DC on pin 3 referred to pin 2: when the Enable signal is set to zero the valve functioning is disabled (zero current to the
solenoid) but the driver current output stage is still active.
Fault Output Signal
Fault output signal indicates fault conditions of the driver (solenoid short circuits/not connected, reference signal cable broken for 4÷20mA input, etc.).
Fault presence corresponds to 0
VDC
, normal working corresponds to 24
VDC (pin 11 referred to pin 2)
: Fault status is not affected by the Enable input signal
8.3 Possible combined options: /IZ
SPOOL POSITION
SIGNAL
(main stage)
F320
9.2 ELECTRONIC CONNECTIONS - 5 PIN COMMUNICATION CONNECTORS
9.1 ELECTRONIC CONNECTIONS - 7 & 12 PIN MAIN CONNECTORS
-PS Serial -BC CANopen -BP PROFIBUS DP
PIN SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION
1 NC do not connect CAN_SHLD Shield +5V for termination
2 NC do not connect NC do not connect LINE-A Bus line (high)
3 RS_GND Signal zero data line CAN_GND Signal zero data line DGND data line and termination Signal zero
4 RS_RX Valves receiving data line CAN_H Bus line (high) LINE-B Bus line (low)
5 RS_TX Valves transmitting data line CAN_L Bus line (low) SHIELD
Standard
7pin
/Z option
12pin
SIGNAL TECHNICAL SPECIFICATIONS NOTES
A 1 V+
Power supply 24 VDC for solenoid power stage (and for driver logic on 7 pin connection)
Input - power supply
Gnd - power supply
B 2 V0 Power supply 0 VDC for solenoid power stage (and for driver logic on 7 pin connection)
- 3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver Input - on/off signal
D 4 INPUT+
Reference analog input: 0 ÷ +10 VDC maximum range (4 ÷ 20 mA for /I option)
standard: differential input; /Z option: common mode INPUT+ referred to AGND
Input - analog signal
E - INPUT -
C 5 AGND
Ground - signal zero for MONITOR signal
signal zero for INPUT+ signal (only for /Z option)
Gnd - analog signal
F 6 MONITOR Monitor analog output: ±10 VDC maximum range (4 ÷ 20 mA for /I option) Output - analog signal
- 7 NC do not connect
- 8 NC do not connect
- 9 VL+ Power supply 24 VDC for driver logic
Input - power supply
Gnd - power supply
- 10 VL0 Power supply 0 VDC for driver logic
- 11 FAULT Fault (0V) or normal working (24V) Output - on/off signal
G PE EARTH Internally connected to the driver housing
9 DIGITAL INTEGRAL DRIVERS -TES - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
COMMUNICATION
CONNECTOR
12 PIN - OPTION /Z
7 PIN - STANDARD
5 PIN reverse key
PROFIBUS DP (-BP)
5 PIN
Serial (-PS) or
CANopen (-BC)
RAMPSBIASSCALE
LINEARIZATION
FIELDBUS
REFERENCE
ENHANCED
DIAGNOSTIC
MAIN CONNECTOR
Note: A minimum time of 300 to 500 ms have be considered between the driver energizing with the 24 V
DC power supply and when the valve is ready
to operate. During this time the current to the valve coils is switched to zero.
(driver view)
(driver view)
(driver view)
Assembly position Any position
Subplate surface finishing Roughness index Ra 0,4 - flatness ratio 0,01/100 (ISO 1101)
Ambient temperature -20°C ÷ +70°C for -T execution; -20°C ÷ +60°C for -TE and TES executions
Fluid Hydraulic oil as per DIN 51524 ... 535 for other fluids see section
Recommended viscosity 15 ÷100 mm
2
/s at 40°C (ISO VG 15÷100)
Fluid contamination class ISO 4406 class 20/18/15 NAS 1638 class 9, in line filters of 10 μm (β
10 _>75 recommended)
Fluid temperature -20°C +60°C (standard seals and water glycol) -20°C +80°C (/PE seals)
11
MAIN CHARACTERISTICS OF PROPORTIONAL THROTTLE CARTRIDGE VALVES
Coil resistance R at 20°C 3 ÷ 3,3 Ω
Max. solenoid current 2,6 A
Max. power 35 Watt
Insulation class H (180°) Due to the occuring surface temperatures of the solenoid coils, the European standards
ISO 13732-1 and EN982 must be taken into account
Protection degree (CEI EN-60529)
IP65 for -T execution; IP67 for -TE and TES executions
Duty factor Continuous rating (ED=100%)
SPOOL POSITION
SIGNAL
(main stage)
10
SOFTWARE TOOLS
The driver configuration and parameters can be easily set with the Atos E-SW programming software, available in three different versions according to the
driver’s communication execution: E-SW-PS (Serial), E-SW-BC (CANopen) and E-SW-BP (PROFIBUS DP).
For a more detailed description of software interface, PC requirements, adapters, cables and terminators, please refer to technical table G500.
Programming software, must be ordered separately:
E-SW-* (mandatory - first supply) = Dvd including E-SW-* software installer and operator manuals; it allows the registration to Atos digital service
E-SW-*-N (optional - next supplies) = as above but not allowing the registration to Atos digital service
On first supply of the E-SW-* software, it is required to apply for the registration in the Atos download area: www.download.atos.com.
Once the registration is completed, the password will be sent by email.
The software remains active for 10 days from the installation date and then it stops until the user inputs his password.
With the password you can also download, in your personal area, the latest releases of the Atos software, manuals, drivers and configuration files.
F320
Regulated flow [l/min]
Reference signal [V]
Regulated flow [l/min]
Reference signal [V]
Amplitude ratio [dB]
Frequency [Hz]
1
23
23
123
23
Phase [degrees]
Amplitude ratio [dB]
Frequency [Hz]
Phase [degrees]
12.3 Regulation diagrams, see note
1 = LIQZO-T*-322L4
12.4 Bode diagrams
stated at nominal hydraulic conditions
2 = LIQZO-T*-322L4: 10% ÷ 90%
3 = LIQZO-T*-322L4: 50% ± 5%
12.5 Regulation diagrams, see note
1 = LIQZO-T*-402L4
12.6 Bode diagrams
stated at nominal hydraulic conditions
2 = LIQZO-T*-402L4: 10% ÷ 90%
3 = LIQZO-T*-402L4: 50% ± 5%
Regulated flow [l/min]
Reference signal [V]
1
2
3
23
Amplitude ratio [dB]
Frequency [Hz]
Phase [degrees]
12.7 Regulation diagrams, see note
1 = LIQZO-T*-502L4
12.8 Bode diagrams
stated at nominal hydraulic conditions
2 = LIQZO-T*-502L4: 10% ÷ 90%
3 = LIQZO-T*-502L4: 50% ± 5%
12
DIAGRAMS (based on mineral oil ISO VG 46 at 50 °C)
12.1 Regulation diagrams, see note
1 = LIQZO-T*-162L4
2 = LIQZO-T*-252L4
Regulated flow [l/min]
Reference signal [V]
2
5
6
5
3
36
Amplitude ratio [dB]
Frequency [Hz]
Phase [degrees]
12.2 Bode diagrams
stated at nominal hydraulic conditions
3 = LIQZO-T*-162L4: 10% ÷ 90%
4 = LIQZO-T*-162L4: 50% ± 5%
5 = LIQZO-T*-252L4: 10% ÷ 90%
6 = LIQZO-T*-252L4: 50% ± 5%
1
4
4
12.9 Dynamic response
The response times in section
and the frequency responses of the bode diagrams in sections 12.2, 12.4, 12.6, 12.8, have to be considered as
average values. For the valves with digital electronics the dynamics performances can be optimized by setting the internal software parameters.
Note:
For the valves with digital electronics, the regulation characteristic can be modified by setting the internal software parameters, see tab. G500.
ADDITIONAL EXTERNAL PILOT PORT CONNECTION
external pilot
(plugged)
Sizes 16 - 50
13
X1 = additional external pilot port connection G1/4”
X1
CH 6
345
IP65
ZBE 06
IP67
02/13
14 INSTALLATION DIMENSIONS [mm]
LIQZO-T LIQZO-TE
666
LIQZO-T LIQZO-TE
LIQZO-TES
Size 16, 25, 32, 40
Size 50
LIQZO-TES
(TES)
345
345
345
345
345
345
ZH-7P or ZM-7P
ZH-7P or ZM-7P
ZH-5P/BP (for -BP)
ZH-5P (for -PS and -BC)
ZH-7P or ZM-7P
ZH-7P or ZM-7P
666
345
345
ZH-5P/BP (for -BP)
ZH-5P (for -PS and -BC)
Dotted line = 12 pin connector ZH-12P for option /Z
-TE and -TES EXECUTION
Size A
85
100
125
B
80
30
39
C
95
105
120
D
79
72
58
E
114
121
120
F
182
171
157
H
150
145
130
Fastening bolts
class 12.9
Weight (Kg)
T TE-TES
N°4 M12x100
N°4 M16x60
N°4 M20x70
25
32
40
65 75 98 80 100 178 150
N°4 M8x90
5,2 5,8
7,5 8,1
10,2 10,8
16 16,6
16
N°4 M20x80
50
23,2 23,8
Tightening
torque
125 Nm
300 Nm
600 Nm
35 Nm
600 Nm
see drawing
135
Mounting surface and cavity: ISO 7368
(see table P006)
(for size 16, 25, 32)
G
16
7
-
25
-
ZBE 06
ZBE 06
ZBE 06
-ALL EXECUTIONS
External piloting X1 = G1/4
MODEL CODES OF POWER SUPPLY AND COMMUNICATION CONNECTORS
(to be ordered separately)
15
666
VALVE VERSION
CONNECTOR CODE
ZH-7P ZM-7P ZH-12P ZH-5P ZH-5P/BP
PROTECTION DEGREE
IP65
Power supply Transducer
IP67 IP67 IP67 IP67 IP67
-T
-TE, -TES
-TE/Z
-TES /Z
serial (-PS)
or CANopen (-BC)
PROFIBUS DP (-BP)
connectors supplied with the valve
DATA SHEET
K500 G200, G210, K500 G210, K500