Proportional reducing valves type RZGO-A*, 3-way
direct operated, without integral pressure transducer, ISO 4401 size 06
Table F015-19/E
RZGO are 3-way proportional pressure
reducing valves,
direct operated without
integral pressure transducer, which provide
pressure
regulation proportional to elec-
tronic reference signal.
They operate in association with electro-
nic drivers, see table 2 which supply the
proportional valve with proper current to
align valve regulation to the reference
signal supplied to the electronic driver.
They are available in different executions:
• -A, without integral pressure transducer.
-AE, -AES, as -A plus analogue (AE) or
digital (AES) integral electronics v.
The reduced pressure is controlled by the
spool c, directly operated by the solenoid x.
The integral electronics v ensures factory
presetting, fine functionality plus valve-to-
valve interchangeability and simplified
wiring and installation.
The electronic main connector b is fully
interchangeable for -AE and -AES
executions. Standard 7 pin connector is
used for power supply, analog input
reference and monitor signals.
12 pin connector is used for option /Z (AES).
Following communication interfaces b
are available for the digital -AES
execution:
-PS, RS232 serial communication
interface. The valve reference signal is
provided with analogue commands via
the 7 (or 12) pins connector b.
• -BC, CANbus interface
• -BP, PROFIBUS-DP interface
The valves with -BC and -BP interfaces
can be integrated into a fieldbus
communication network and thus digitally
operated by the machine control unit.
The coils are fully plastic encapsulated
(insulation class H), and the valves have
antivibration, antishock and weather-proof
features.
Surface mounting: ISO 4401 size 06.
Max flow: 12 l/min.
Max pressure: 210 bar.
F015
RZGO-AES-PS-010/*
RZGO
Proportional pressure
reducing valve size 06
A = without integral transducer
AE = as A plus integral electronics
AES = as A plus integral digital electronics
Communication interfaces (only for AES)
PS = Serial
BC = CANopen
BP = PROFIBUS DP
Series number
Syntethic fluids
WG = water-glycol
PE = phosphate ester
32 **AES––/ *
1 MODEL CODE
010PS
Pressure range
32 = 32 bar
100 = 100 bar
210 = 210 bar
*//
Valve body
Proportional solenoid
Spool
Integral electronics
Main connector
Communication connector
Screw for air bleeding
2
ELECTRONIC DRIVERS FOR RZGO
Valve model
Drivers model
Data sheet
E-MI-AC-01F
G010
E-BM-AC-01F E-ME-AC-01F E-RP-AC-01F
G025 G035 G100
E-RI-AE
G110
E-RI-AES
G115
-A -AE -AES
Note: for power supply and communication connector see section
E-MI-AS-IR
E-BM-AS-PS
G020
G030
15
Configuration:
010 = regulation on port P, discharge in T
Options for -A execution, see section
5
:
6 = with 6 V
DC
coil instead of standard
12V
DC
coil
18 = with 18 V
DC
coil instead of standard
12V
DC
coil
Electronic options for -AE execution,
see section
7
:
I = current reference input (4÷20 mA)
Q = enable signal
Electronic options for -AES execution,
see section
9
:
I = current reference input (4÷20 mA)
Z =
double power supply, enable fault and
monitor signals (12 pin connector)
www.atos.com
www.atos.com
45
1,5
3
2
100 210
3
HYDRAULIC CHARACTERISTICS (based on mineral oil ISO VG 46 at 50 °C)
Hydraulic symbols
Valve model
Max regulated pressure (Q = 1 l/min) [bar]
Min regulated pressure [bar]
Max pressure at port P [bar]
Max pressure at port T [bar]
Max flow [l/min]
Response time 0 - 100% step signal
[ms]
(depending on installation)
Hysteresis [% of the max pressure]
Linearity [% of the max pressure]
Repeatability [% of the max pressure]
RZGO-AE RZGO-AES
32
0,8 (or actual value in T port)
315
210
12
Above performance data refer to valves coupled with Atos electronic drivers, see section
2
.
RZGO-A
RZGO proportional valves are CE marked according to the applicable Directives (e.g. Immunity/Emission EMC Directive).
Installation, wirings and start-up procedures must be performed according to the general prescriptions shown in table F003 and in the installation notes
supplied with relevant components.
The electrical signals of the valve (e.g. monitor signals) must not be directly used to activate safety functions, like to switch-ON/OFF the machine’s safety
components, as prescribed by the European standards (Safety requirements of fluid technology systems and components-hydraulics, EN-982).
4
GENERAL NOTES
6
CONNECTIONS FOR -A EXECUTION
Signal description
SUPPLY
SUPPLY
GND
PIN
1
2
3
SOLENOID POWER SUPPLY CONNECTOR
1
2
3
7 ANALOG INTEGRAL DRIVERS -AE - OPTIONS
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to the driver power supply.
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers
Reference input signal
- analog differential input with 0÷+10 VDC nominal range (pin D,E), proportional to desired coil current
Monitor output signal
- analog output signal proportional to the actual valve’s coil current (1V monitor = 1A coil current)
Following options are available to adapt standard execution to special application requirements:
7.1 Option /I
It provides the 4÷20 mA current reference signal instead of the standard 0÷+10 V
DC. Monitor output signal is still the standard 0÷+10 VDC
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
7.2 Option /Q
It provides the possibility to enable or disable the valve functioning without cutting the power supply (the valve functioning is disabled but the driver cur-
rent output stage is still active). To enable the driver supply a 24V
DC on the enable input signal.
7.3 Possible combined option: /IQ
5
OPTIONS FOR -A EXECUTION
5.1 Option /6
6
VDC coil instead of standard 12 VDC, to be used in case of power supply 12 VDC
5.2 Option /18
18
VDC coil instead of standard 12 VDC, to be used with electronic drivers not supplied by Atos
REGULATIONS AND SWITCHES
7 PIN - STANDARD
MAIN CONNECTOR
BIAS
SCALE
RAMPS
positive bias adjust
(driver view)
positive scale adjust
B1:
S1:
(remove the rear cover)
8 ANALOG INTEGRAL DRIVERS -AE - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
PIN SIGNAL
TECHNICAL SPECIFICATIONS
NOTES
A V+ Power supply 24 VDC for solenoid power stage and driver logic Input - power supply
B V0 Power supply 0 VDC for solenoid power stage and driver logic Gnd - power supply
C
(1)
AGND Ground - signal zero for MONITOR signal Gnd - analog signal
ENABLE Enable (24 VDC) or disable (0 VDC) the driver (for /Q option) Input - on/off signal
D INPUT+
Reference analog differential input: 0÷+10 VDC maximum range (4 ÷ 20 mA for /I option)
Normal working range 0÷+10 V
DC (4 ÷ 20 mA for /I option)
Input - analog signal
E INPUT -
F MONITOR
Monitor analog output:
0÷+10 V
DC
maximum range
Output - analog signal
G EARTH Internally connected to the driver housing
Note: (1) with /Q option ENABLE signal replaces AGND on pin C; MONITOR signal is reffered to pin B.
A minimum time of 60ms to 160ms have be considered between the driver energizing with the 24 V
DC power supply and when the valve is ready
to operate. During this time the current to the valve coils is switched to zero
9 DIGITAL INTEGRAL DRIVERS -AES - OPTIONS
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to each driver power supply
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers.
Reference input signal
- analog differential input with 0÷+10 VDC nominal range (pin D,E), proportional to desired coil current
Monitor output signal
- analog output signal proportional to the actual valve’s coil current (1V monitor = 1A coil current)
Following options are available to adapt standard execution to special application requirements:
9.1 Option /I
It provides 4÷20 mA current reference signal instead of the standard 0÷+10 V
DC. Monitor output signal is still the standard 0÷+10 VDC
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
9.2 Option /Z
It provides on a 12 pin main connector the above standard features plus:
Logic power supply
Option /Z provides separate power supply for the solenoid (pin 1, 2) and for the digital electronic circuits (pin 9, 10).
Cutting solenoid power supply allows to interrupt the valve functioning but keeping energized the digital electronics thus avoiding fault conditions of the
machine fieldbus controller. This condition allows to realize safety systems in compliance with European Norms EN13849-1 (ex EN954-1).
Enable Input Signal
To enable the driver, supply a 24V
DC on pin 3 referred to pin 2: when the Enable signal is set to zero the valve functioning is disabled (zero current to
the solenoid) but the driver current output stage is still active. This condition does not comply with European Norms EN13849-1 (ex EN954-1).
Fault Output Signal
Fault output signal indicates fault conditions of the driver (solenoid short circuits/not connected, reference signal cable broken for 4÷20mA input, etc.).
Fault presence corresponds to 0
VDC
, normal working corresponds to 24
VDC (pin 11 referred to pin 2)
: Fault status is not affected by the Enable input signal
.
9.3 Possible combined option: /IZ
Selector SW
Dither frequency
[Hz]
SW1 SW2 SW3 SW4
ON
ON
ON
ON ON
ON ON
ON ON ON
ON ON ON
ON ON ON
ON ON ON
ON ON ON ON
The dither frequency is factory pre-
set at 200 Hz and its regulation may
be adjusted after contact with Atos
technical department
100
130
160
200 (Standard)
230
270
300
380
430
470
500
ramp for increasing reference signal
ramp for decreasing reference signal
RU:
RD:
8.1 ELECTRONIC CONNECTIONS - 7 PIN MAIN CONNECTORS
dither frequency selector (see table beside)
SW:
B1
S1
H
H
H
H
SW
H
RU
RD
ON
OFF
F015
10 DIGITAL INTEGRAL DRIVERS -AES - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
COMMUNICATION
CONNECTOR
12 PIN - OPTION /Z
7 PIN - STANDARD
5 PIN reverse key
PROFIBUS DP (-BP)
5 PIN
Serial (-PS) or
CANopen (-BC)
RAMPS
BIASSCALE
MAIN CONNECTOR
(driver view)
(driver view)
(driver view)
LINEARIZATION
Assembly position Any position
Subplate surface finishing Roughness index, flatness ratio 0,01/100 (ISO 1101)
Ambient temperature -20°C ÷ +70°C for -A execution; -20°C ÷ +60°C for -AE and -AES executions
Fluid Hydraulic oil as per DIN 51524 ... 535 for other fluids see section
1
Recommended viscosity 15 ÷100 mm
2
/s at 40°C (ISO VG 15÷100)
Fluid contamination class ISO 18/15 achieved with in line filters of 10 μm and β
10 _>75 (recommended)
Fluid temperature -20°C +60°C (standard and /WG seals) -20°C +80°C (/PE seals)
10.2 ELECTRONIC CONNECTIONS - 5 PIN COMMUNICATION CONNECTORS
10.1 ELECTRONIC CONNECTIONS - 7 & 12 PIN MAIN CONNECTORS
-PS Serial -BC CANopen -BP PROFIBUS DP
PIN SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION
1 NC do not connect CAN_SHLD Shield +5V for termination
2 NC do not connect NC do not connect LINE-A Bus line (high)
3 RS_GND Signal zero data line CAN_GND Signal zero data line DGND data line and termination Signal zero
4 RS_RX Valves receiving data line CAN_H Bus line (high) LINE-B Bus line (low)
5 RS_TX Valves transmitting data line CAN_L Bus line (low) SHIELD
Standard
7pin
/Z option
12pin
SIGNAL TECHNICAL SPECIFICATIONS NOTES
A 1 V+
Power supply 24 VDC for solenoid power stage (and for driver logic on 7 pin connection)
Input - power supply
Gnd - power supply
B 2 V0 Power supply 0 VDC for solenoid power stage
(and for driver logic on 7 pin connection)
- 3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver Input - on/off signal
D 4 INPUT+
Reference analog input: ±10 VDC maximum range (4 ÷ 20 mA for /I option)
Normal working range 0÷+10 V
DC (4 ÷ 20 mA for /I option)
standard: differential input; /Z option: common mode INPUT+ referred to AGND
Input - analog signal
E - INPUT -
C 5 AGND
Ground - signal zero for MONITOR signal
signal zero for INPUT+ signal ( only for /Z option)
Gnd - analog signal
F 6 MONITOR Monitor analog output: ±10 VDC maximum range Output - analog signal
- 7 NC do not connect
- 8 NC do not connect
- 9 VL+ Power supply 24 VDC for driver logic
Input - power supply
Gnd - power supply
- 10 VL0 Power supply 0 VDC for driver logic
- 11 FAULT Fault (0 VDC) or normal working (24 VDC) Output - on/off signal
G PE EARTH Internally connected to the driver housing
11
SOFTWARE TOOLS
Note: A minimum time of 270 to 340 ms have be considered between the driver energizing with the 24 VDC power supply and when the valve is ready
to operate. During this time the current to the valve coils is switched to zero.
12 MAIN CHARACTERISTICS OF PROPORTIONAL REDUCING VALVES
Coil resistance R at 20°C 3 ÷ 3.3 Ω for standard 12 V
DC
coil; 2 ÷ 2,2 Ω for 6 V
DC
coil; 13 ÷ 13,4 Ω for 18 V
DC
coil
Max solenoid current
2,4 A (1,8 A for version /32) for standard 12 V
DC
coil; 3 A (2,25 A for version /32) for 6 V
DC
coil;1 A (0,8 A for version /32) for 18 V
DC
coil
Max power 40 Watt
Protection degree (CEI EN-60529)
IP65 for -A execution; IP65÷67 for -AE and -AES executions, depending to the connector type, see sect.
Duty factor Continuous rating (ED=100%)
15
The functional parameters of digital valves, as the bias, scale ramp and linearization of the regulation characteristic, can be easily set and optimized with the
Atos E-SW programming software, available in three different versions according to the driver’s communication interfacing: E-SW-PS (Serial), E-SW-BC
(CANopen) and E-SW-BP (PROFIBUS DP).
A proper connection is required between the PC and the electronic driver communication port: for a more detailed description of software interface, PC
requirements, adapters, cables and terminators, please see table G500.
Proportional valves with fieldbus communication interface (-BC and -BP) can be directly managed by the machine control unit; it is required to implement
in the machine control the standard communication as described in the user manuals supplied with the relevant programming software. For detailed
description of available fieldbus feature, see table G510.
On first supply of the E-SW software, it is required to apply for the registration in the Atos download area: www.download.atos.com
Once the registration is completed, the password will be sent by email.
The software remains active for 10 days from the installation date and then it stops until the user inputs his password.
With the password you can also download, in your personal area, the latest releases of the Atos software, manuals, drivers and configuration files.
F015
13
DIAGRAMS (based on mineral oil ISO VG 46 at 50 °C)
Pressure at port A [% of the max]
Reference signal [% of the max]
13.1 Regulation diagrams
with flow rate Q = 1 l/min
1 = RZGO-A, RZGO-AE, RZGO-AES
13.2 Pressure/flow diagrams
with reference pressure set with Q = 1 l/min
2 = RZGO-A, RZGO-AE, RZGO-AES
13.3 Pressure drop/flow diagram
with zero reference signal
3 = Pressure drops vs. flow P-A (for all the
executions)
4 = Pressure drops vs. flow A-T (for all the
executions)
Differential pressure P-A [bar]
Flow [l/min]
Differential pressure A-T [bar]
Flow [l/min]
1
2
34
Notes:
The presence of counter pressure at port T
can affect the effective pressure regulation.
13.4 Dynamic response
The response times in section 3 have to be considered as average values.
The pressure variation in consequence of a modification of the reference input signal to the valve is affected by the stiffness of the hydraulic circuit:
greater is the stiffness of the circuit, faster is the dynamic response.
[PA]
Flow [l/min]
[AT]
Regulated pressure at port A [% of the max]
14 INSTALLATION DIMENSIONS [mm]
ISO 4401: 2005
Mounting surface: 4401-03-02-0-05 (see table P005)
Fastening bolts:
4 socket head screws M5x50 class 12.9
Tightening torque = 8 Nm
Seals: 4 OR 108
Ports P, A, T: Ø = 5 mm
Port B: not used
05/09
SP-666
MODEL CODES OF POWER SUPPLY AND COMMUNICATION CONNECTORS (to be ordered separately)
15
connectors supplyed with the valve
VALVE VERSION
CONNECTOR CODE
SP-ZH-7P SP-ZM-7P SP-ZH-12P SP-ZH-5P SP-ZH-5P/BP
PROTECTION DEGREE
IP65 IP67 IP67 IP65 IP67 IP67
-A -AE, -AES -AES/Z
-Serial (-PS)
or CANopen (-BC)
PROFIBUS DP (-BP)
DATA SHEET
K500 G110, G115, K500
G115, K500
Mass: 2,5 Kg
Mass: 1,8 Kg
RZGO-AE
RZGO-AES-*
Mass: 2,7 Kg
RZGO-A
SP-666
SP-ZH-7P or SP-ZM-7P
SP-ZH-5P/BP (for -BP)
SP-ZH-5P (for -PS and -BC)
x
SP-ZH-7P or SP-ZM-7P
y
y
y
= screw for air bleeding
y
Dotted line = 12 pin connector SP-ZH-12P for option /Z
x