www.atos.com
Servoproportional valves type DLHZO-TE and DLKZOR-TE
sleeve execution, direct operated, with position transducer, ISO 4401 size 06 and 10
Table F180-17/E
1 MODEL CODE
DLKZOR-TE-160
DLHZO
DLHZO = size 06
DLKZOR = size 10
T = with position transducer
TE = as T with integral analog
electronics
TES = with digital electronics
Valve configuration, see section
4 = spring offset with fail safe
6 = spring offset
0 = zero overlapping
0, 1, 3, 5, 7 = spool size, see section
Notes:
(1) Spool type D, DT and T are available only for valve configuration with fail safe position DLHZO-*-040 and DLKZOR-*-140
Fail safe configuration (de-energized solenoid):
1 = A, B, P, T with positive overlapping (20% of spool stroke)
3 = P positive overlapping (20% of spool stroke); A, B, T negative
Series number
TES PS 40L-0*/73 **/ *---
Valve size , see section
0 = ISO 4401 size 06 1 = ISO 4401 size 10
Communication interfaces (only for TES)
PS = Serial
BC = CANopen
BP = PROFIBUS DP
DLHZO and DLKZOR are high
performance servoproportional valves,
direct operated, with sleeve execution and
LVDT position transducer, which provide
both directional and non compensated
flow control according to the electronic
reference signal.
They operate in association with electronic
drivers, see section
, which supply the
proportional valves with proper current to
align valve regulation to the reference
signal supplied to the electronic driver.
They are available in different executions:
-T, with integral position transducer ;
-TE, -TES as -T plus analog (TE) or
digital (TES) integral electronics .
The 4-way spool is sliding into a
precision - machined and hardened sleeve
for maximum overlapping accuracy.
The sleeve is mechanically forced into a
5-chambers body .
The spool is directly
operated by a proportional solenoids and
it is controlled in closed loop position by
means of the LVDT position transducer
.
The integral electronics ensures factory
presetting, fine functionality plus valve-to-
valve interchangeability and simplified
wiring and installation.
The electronic main connector is fully
interchangable for -TE and -TES
executions.
Standard 7 pin main connector is used for
power supply, analog input reference and
monitor signals.
12 pin connector is used for options /Z
and /S*.
The special /S* options add a closed loop
control of pressure (/SP) or force (/SF and
/SL) to the basic closed loop spool posi-
tion one.
Following communication interfaces
are
available for the digital -TES execution:
-PS, Serial communication interface for
configuration, monitoring and firmware
updating through Atos PC software
• -BC, CANopen interface
• -BP, PROFIBUS DP interface
The valves with -BC and -BP interfaces
can be integrated into a fieldbus
communication network and thus digitally
operated by the machine control unit.
The coils are fully plastic encapsulated
(insulation class H) and the valves have
antivibration, antishock and weather-proof
features.
Mounting surface: ISO 4401 sizes 06 and 10.
Max flow respectively up to 40 l/min and
100 l/min with valve differential pressure
Δp = 70 bar, see table
.
Max pressure = 350 bar
Hydraulic options, see section
:
B = solenoid, integral electronics and
position transducer at side of port A
Y = external drain
Electronics options, for -TE execution
see section
:
F = fault signal
I =current reference input and monitor
(4÷20 mA)
Q = enable signal
Z = enable, fault and monitor signals (12
pin connector)
Electronics options, for -TES execution
see section
:
I =current reference input and monitor
(4÷20mA)
Z =
double power supply, enable fault and
monitor signals (12 pin connector)
Special options for -TES execution
see section
:
SF =
additional closed loop force control,
with two remote pressure transducers
SL = additional closed loop force control
with one remote load cell
SP = additional closed loop pressure
control with one remote pressure
transducer
C = current feedback interface for transdu-
cer(s) only for options /SF, /SL, /SP
Spool type (regulating characteristics)
L = linear;
D = differential-linear (as L, but with P-A = Q, P-B = Q/2)
(2)
DT = as D, but with non linear regulation (1)
T = not linear regulation
(1)
V = progressive
/
2 ELECTRONIC DRIVERS
Valve model
Data sheet
Drivers model E-ME-T
G140
-T
E-RI-TE
G200
-TE
E-RI-TES
G210
-TES
Note: For power supply and communication connector see section 15 and 17
Position transducer
Integral electronics
Main connector
Valve body
Spool
Sleeve
Proportional solenoid
F180
E-RI-TES / SF, SL, SP
G212
-TES / SF, SL, SP
Seals material:
omit for NBR (mineral
oil & water glycol)
PE = FPM
TE and TES executions included in this table are available only for running supplies or spare parts
For new applications it is suggested new TEB and TES executions, see table FS180
2
Valve model
Pressure limits [bar]
DLHZO-T*
ports P, A, B = 350;
T = 210 (250 with external drain /Y)
3
HYDRAULIC CHARACTERISTICS (based on mineral oil ISO VG 46 at 50 °C)
DLKZOR-T*
ports P, A, B =
315;
T = 210
(250 with external drain /Y)
Spool
Leakage [cm
3
/min] at P = 100 bar (2)
Fail safe connections
Fail safe 1
Fail safe 3
DLHZO
DLKZOR
Fail safe 3
Response time
(5) [ms]
Hysteresis [%]
Thermal drift
10
0,1%
P AP BA TB T
50 70 70 50
50 70 - -
- - 15÷30 10÷20
- - 40÷60 25÷40
15
0,1%
Hydraulic
symbols
*60-L*1
*60-V*1
b
b
*60-L*1/B
*60-V*1/B
a
a
a
b
zero point displacement < 1% at ΔT = 40°C
Signal description
OUTPUT SIGNAL
SUPPLY -15 V
DC
SUPPLY +15 VDC
GND
PIN
1
2
3
4
POSITION TRANSDUCER CONNECTOR
6
CONNECTIONS FOR -T EXECUTION
DLHZO and DLKZOR servoproportional valves are CE marked according to the applicable Directives (e.g. Immunity/Emission EMC Directive and Low Voltage Directive).
Installation, wirings and start-up procedures must be performed according to the general prescriptions shown in table F003 and in the installation notes
supplied with relevant components.
The electrical signals of the valve (e.g. monitor signals) must not be directly used to activate safety functions, like to switch-ON/OFF the machine’s safety
components, as prescribed by the European standards (Safety requirements of fluid technology systems and components-hydraulics, EN-982).
Signal description
SUPPLY
SUPPLY
GND
PIN
1
2
3
SOLENOID POWER SUPPLY CONNECTOR
1
2
3
1
2
3
4
5
GENERAL NOTES
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to the driver power supply
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers
Reference input signal
- analog differential input with ±10 VDC nominal range (pin D, E), proportional to desired valve spool position
Monitor output signal
- analog output signal proportional to the actual valve’s spool position with ±10 VDC nominal range
Following options are available to adapt standard execution to special application requirements:
7.1 Option /F
It provides a Fault output signal in place of the Monitor output signal, to indicate fault conditions of the driver (cable interruption of spool transducers or
reference signal - for /I option): Fault presence corresponds to 0 V
DC, normal working corresponds to 24 VDC.
7.2 Option /I
It provides the 4÷20 mA current reference and monitor signals instead of the standard ±10 VDC
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
7.3 Option /Q
It provides the possibility to enable or disable the valve functioning without cutting the power supply (the valve functioning is disabled but the driver cur-
rent output stage is still active). To enable the driver supply a 24VDC on the enable input signal.
7.4 Option /Z
This option includes /F and /Q features, plus the Monitor output signal.
When the driver is disabled (
0 VDC
on Enable signal) Fault output is forced to 0
VDC
.
7.5 Possible combined options: /FI and /IZ
7 ANALOG INTEGRAL DRIVERS -TE - OPTIONS
4
HYDRAULIC OPTIONS
4.1 Option /B Solenoid, integral electronics and position transducer at side of port A.
4.2 Option /Y External drain is mandatary if the pressure in port T exceeds 160 bar.
L0
Max flow
(1) [l/min]
at Δp = 30 bar
at Δp = 70 bar
max permissible flow
2,5
4
8
L1 V1 L3 V3 L5 T5 L7 T7 V7 D7 DT7 L3 L7 T7 V7 D7 DT7
4,5
7
14
5
8
16
9
14
30
13
20
40
18
28
50
26
40
70
26÷13
40÷20
70÷40
40
60
90
60
100
160
60÷33
100÷50
160÷80
Notes:
Above performance data refer to valves coupled with Atos electronic drivers,
see sections .
The flow regulated by the directional proportional valves is not pressure compensated, thus it is affected by the load variations.To keep costant the regulated
flow under different load conditions, modular pressure compensators are available (see tab. D150).
(1) For different
Δ
p, the max flow is in accordance to the diagrams in section 13.2
(2) Referred to spool in neutral position and 50°C oil temperature.
(3) Referred to spool in fail safe position and 50°C oil temperature.
(4) Referred to spool in fail safe position at
Δ
p = 35 bar per edge and
50°C oil temperature.
(5) 0-100% step signal
<200
<300 <500
<200 <900 <200
<1000 <1500 <400
<100 <100 <150 <200 <200<700
<1200
<400 <400
*40-L*3/B
*40-D*3/B
*40-DT*3/B
*40-T*3/B
*40-V*3/B
*40-L*1/B
*40-D*1/B
*40-DT*1/B
*40-T*1/B
*40-V*1/B
*40-L*3
*40-D*3
*40-DT*3
*40-T*3
*40-V*3
*40-L*1
*40-D*1
*40-DT*1
*40-T*1
*40-V*1
Leakage [cm
3
/min]
at P = 100 bar
(3)
Flow [l/min] (4)
9 DIGITAL INTEGRAL DRIVERS -TES - OPTIONS
8 ANALOG INTEGRAL DRIVERS -TE - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
12 PIN - OPTION /Z
REGULATIONS AND LED
7 PIN - STANDARD
MAIN CONNECTOR
BIAS
SCALE
DIAGNOSTIC
B2
B1
S2
S1
bias adjust
LED:
LED
(driver view)
(driver view)
8.1 ELECTRONIC CONNECTIONS - 7 & 12 PIN MAIN CONNECTORS
not working
positive scale adjust
negative scale adjust
OFF normal working; ON fault presence
B1:
B2:
S1:
S2:
Standard driver execution provides on the 7 pin main connector:
Power supply
- 24VDC must be appropriately stabilized or rectified and filtered; a 2,5 A safety fuse is required in series to each driver power supply
Apply at least a 10000 μF/40 V capacitance to single phase rectifiers or a 4700 μF/40 V capacitance to three phase rectifiers
Reference input signal
- analog differential input with ±10VDC nominal range (pin D,E), proportional to desired valve spool position
Monitor output signal
- analog output signal proportional to the actual valve’s spool position with ±10VDC nominal range
Following options are available to adapt standard execution to special application requirements:
9.1 Option /I
It provides 4÷20 mA current reference and monitor signals instead of the standard ±10 V.
It is normally used in case of long distance between the machine control unit and the valve or where the reference signal can be affected by electrical
noise; the valve functioning is disabled in case of reference signal cable breakage.
9.2 Option /Z
It provides, on the 12 pin main connector, the following additional features:
Logic power supply
Separated power supply for the solenoid (pin 1, 2) and for the digital electronic circuits (pin 9, 10).
Cutting solenoid power supply allows to interrupt the valve functioning but keeping energized the digital electronics thus avoiding fault conditions of the
machine fieldbus controller. This condition allows to realize safety systems in compliance with European Norms EN13849-1 (ex EN954-1).
Enable Input Signal
To enable the driver, supply 24V
DC on pin 3 referred to pin 2: when the Enable signal is set to zero the valve functioning is disabled (zero current to the
solenoid) but the driver current output stage is still active.
Fault Output Signal
Fault output signal indicates fault conditions of the driver (solenoid short circuits/not connected, reference signal cable broken for 4÷20mA input, etc.).
Fault presence corresponds to 0
VDC
, normal working corresponds to 24
VDC (pin 11 referred to pin 2)
: Fault status is not affected by the Enable input signal
9.3 Options /SP, /SF and /SL
These options add the closed loop control of pressure (/SP) or force (/SF and /SL) to the basic functions of proportional directional valves: a dedicated
software alternates pressure (force) and valve’s spool position controls depending on the actual hydraulic system conditions.
A dedicated connector is available for the additional transducers that are required to be interfaced to the valve’s driver (1 pressure transducer for /SP,
2 pressure transducers for /SF or 1 load cell for /SL).
Main 12 pin connector is the same as /Z option plus two analog signals specific for the pressure (force) control: one for reference (pin 7) and one for
monitor (pin 8).
For futher details please refer to the driver technical table G212.
9.4 Options /C
Options /CSP, /CSF and /CSL are available to connect pressure (force) transducers with 4 ÷ 20mA current output signal.
9.5 Possible combined options: /ISP, /ISF, /ISL, /CSP, /CSF, /CSL, /CISP, /CISF, /CISL and /IZ
(remove the rear cover)
Standard
7pin
/Z option
12pin
SIGNAL
TECHNICAL SPECIFICATIONS
NOTES
A 1 V+ Power supply 24 VDC for solenoid power stage and driver logic
Input - power supply
Gnd - power supply
B 2 V0 Power supply 0 VDC for solenoid power stage and driver logic
C
(1)
7 AGND Ground - signal zero for MONITOR signal (for standard and /Z options) Gnd - analog signal
3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver (for /Q and /Z options) Input - on/off signal
D 4 INPUT+
Reference analog differential input: ±10 VDC maximum range (4 ÷ 20 mA for /I option)
Input - analog signal
E 5 INPUT -
F
(2)
6 MONITOR Monitor analog output: ±10 VDC maximum range (4 ÷ 20 mA for /I option) Output - analog signal
11 FAULT Fault (0V) or normal working (24V) (for F and /Z options) Output - on/off signal
- 8 R_ENABLE Repeat Enable - output repetition of Enable input Output - on/off signal
- 9 NC do not connect
Output - on/off signal
Output - on/off signal
- 10 NC do not connect
G PE EARTH
Internally connected to the driver housing
Notes (1) with /Q option ENABLE signal replaces AGND on pin C; MONITOR signal is reffered to pin B
(2) with /F option FAULT signal replaces MONITOR on pin F.
A minimum time of 50ms to 100ms have be considered between the driver energizing with the 24 V
DC power supply and when the valve is ready
to operate. During this time the current to the valve coils is switched to zero.
F180
10.2 ELECTRONIC CONNECTIONS - 5 PIN COMMUNICATION CONNECTORS
10.1 ELECTRONIC CONNECTIONS - 7 & 12 PIN MAIN CONNECTORS
-PS Serial -BC CANopen -BP PROFIBUS DP
PIN SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION SIGNAL TECHNICAL SPECIFICATION
1 NC do not connect CAN_SHLD Shield +5V for termination
2 NC do not connect NC do not connect LINE-A Bus line (high)
3 RS_GND Signal zero data line CAN_GND Signal zero data line DGND data line and termination Signal zero
4 RS_RX Valves receiving data line CAN_H Bus line (high) LINE-B Bus line (low)
5 RS_TX Valves transmitting data line CAN_L Bus line (low) SHIELD
Standard
7pin
/Z option
12pin
SIGNAL TECHNICAL SPECIFICATIONS NOTES
A 1 V+
Power supply 24 VDC for solenoid power stage (and for driver logic on 7 pin connection)
Input - power supply
Gnd - power supply
B 2 V0 Power supply 0 VDC for solenoid power stage (and for driver logic on 7 pin connection)
- 3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver Input - on/off signal
D 4 INPUT+
Reference analog input: ±10 VDC maximum range (4 ÷ 20 mA for /I option)
standard: differential input; /Z option: common mode INPUT+ referred to AGND
Input - analog signal
E - INPUT -
C 5 AGND
Ground - signal zero for MONITOR signal
signal zero for INPUT+ signal ( only for /Z option)
Gnd - analog signal
F 6 MONITOR Monitor analog output: ±10 VDC maximum range (4 ÷ 20 mA for /I option) Output - analog signal
- 7 NC do not connect ( pressure/force input for /SP, /SF and /SL options, see 9.3 )
- 8 NC do not connect ( pressure/force monitor for /SP, /SF and /SL options, see 9.3 )
- 9 VL+ Power supply 24 VDC for driver logic
Input - power supply
Gnd - power supply
- 10 VL0 Power supply 0 VDC for driver logic
- 11 FAULT Fault (0V) or normal working (24V) Output - on/off signal
G PE EARTH Internally connected to the driver housing
10 DIGITAL INTEGRAL DRIVERS -TES - MAIN FUNCTIONS AND ELECTRONIC CONNECTIONS
COMMUNICATION
CONNECTOR
12 PIN - OPTION /Z, /SP, /SF and /SL
7 PIN - STANDARD
5 PIN reverse key
PROFIBUS DP (-BP)
5 PIN
Serial (-PS) or
CANopen (-BC)
RAMPSBIASSCALE
LINEARIZATION
FIELDBUS
REFERENCE
ENHANCED
DIAGNOSTIC
REMOTE PRESSURE
(FORCE) TRANDUCER
(for /SP, /SF and /SL)
11
SOFTWARE TOOLS
MAIN CONNECTOR
Note: A minimum time of 300 to 500 ms have be considered between the driver energizing with the 24 VDC power supply and when the valve is ready
to operate. During this time the current to the valve coils is switched to zero.
(driver view)
(driver view)
(driver view)
The driver configuration and parameters can be easily set with the Atos E-SW programming software, available in three different versions according to the
driver’s communication execution: E-SW-PS (Serial), E-SW-BC (CANopen) and E-SW-BP (PROFIBUS DP).
For a more detailed description of software interface, PC requirements, adapters, cables and terminators, please refer to technical table G500.
Programming software, must be ordered separately:
E-SW-* (mandatory - first supply) = Dvd including E-SW-* software installer and operator manuals; it allows the registration to Atos digital service
E-SW-*-N (optional - next supplies) = as above but not allowing the registration to Atos digital service
On first supply of the E-SW-* software, it is required to apply for the registration in the Atos download area: www.download.atos.com.
Once the registration is completed, the password will be sent by email.
The software remains active for 10 days from the installation date and then it stops until the user inputs his password.
With the password you can also download, in your personal area, the latest releases of the Atos software, manuals, drivers and configuration files.
Assembly position Any position
Subplate surface finishing Roughness index Ra 0,4 - flatness ratio 0,01/100 (ISO 1101)
Ambient temperature -20°C ÷ +70°C for -T execution; -20°C ÷ +60°C for -TE and TES executions
Fluid Hydraulic oil as per DIN 51524 ... 535 for other fluids see section
Recommended viscosity 15 ÷100 mm
2
/s at 40°C (ISO VG 15÷100)
Fluid contamination class ISO 4406 class 20/18/15 NAS 1638 class 9, in line filters of 10 μm (β
10 _>75 recommended)
Fluid temperature -20°C +60°C (standard seals and water glycol) -20°C +80°C (/PE seals)
12 MAIN CHARACTERISTICS OF PROPORTIONAL DIRECTIONAL VALVES
Valve model DLHZO-T* DLKZOR-T*
Coil resistance R at 20°C 3 ÷ 3,3 Ω
3,8 ÷ 4,1
Ω
Max. solenoid current 2,6 A 3 A
Max. power 35 Watt 40 Watt
Insulation class H (180°) Due to the occuring surface temperatures of the solenoid coils, the European standards
ISO 13732-1 and EN982 must be taken into account
Protection degree (CEI EN-60529)
IP65 for -T execution; IP67 for -TE and -TES executions
Duty factor Continuous rating (ED=100%)
13
DIAGRAMS (based on mineral oil ISO VG 46 at 50 °C)
13.1 Regulation diagrams
1 = Linear spools L
2 = Differential - linear spool D7
F180
Nominal flow [%]
Nominal flow [%]
Reference signal [Volt] Reference signal [Volt]
12
3 = Differential non linear spool DT7
4 = Non linear spool T5 (only for DLHZO)
Nominal flow [%]
Reference signal [Volt]
3
Note:
Hydraulic configuration vs. reference signal:
Standard:
Reference signal 0 ÷+10 V P A / B T
12÷20 mA
Reference signal 0 ÷-10 V P B / A T
4÷12 mA
option /B:
Reference signal 0 ÷+10 V P B / A T
12÷20 mA
Reference signal 0 ÷-10 V P A / B T
4÷12 mA
Nominal flow [%]
Reference signal [Volt]
4
Nominal flow [%]
Reference signal [Volt]
5
Nominal flow [%]
Reference signal [Volt]
6
5 = Non linear spool T7
6 = Progressive spool V
7 = Pressure gain
Δp AB [%P]
Spool stroke [%]
7
T5 and T7 spool types are specific for fine
low flow control in the range from 0 to 60%
(T5) and 0 to 40% (T7) of max spool stroke.
The non linear characteristics of the spool is
compensated by the electronic driver, so the
final valve regulation is resulting linear
respect the reference signal (dotted line).
DT7 has the same characteristic of T7 but it
is specific for applications with cylinders with
area ratio 1:2
}
}
}
}
13.2 Flow /Δp diagrams
Stated at 100% of spool stroke
DLHZO:
1 = spool L7, T7, V7, D7, DT7
2 = spool L5, T5
3 = spool V3
4 = spool L3
5 = spool L1, V1
6 = spool L0
DLKZOR:
7 = spool L7, T7, V7, D7, DT7
8 = spool L3
13.3 Bode diagrams
Stated at nominal hydraulic conditions
DLHZO:
1 = ± 100% nominal stroke
2 = ± 5% nominal stroke
DLKZOR:
3 = ± 100% nominal stroke
4 = ± 5% nominal stroke
Flow rate [l/min]
Valve pressure drop Δp [bar]
Flow rate [l/min]
Valve pressure drop Δp [bar]
Amplitude ratio [dB]
Frequency [Hz]
Phase [degree]
Amplitude ratio [dB]
Frequency [Hz]
Phase [degree]
12
12
34
34
7
8
1
2
3
4
13.4 Dynamic response
The response times in section
have to be considered as average values.
For the valves with digital electronics the dynamics performances can be optimized by setting the internal software parameters.
5
6
14 INSTALLATION DIMENSIONS [mm]
Mass: 2,8 kg
Mass: 2,3 kg
DLHZO-T
ISO 4401: 2005
Mounting surface: 4401-03-02-0-05
(see table P005)
(for /Y version, surface: 4401-03-03-0-05 without X port)
Fastening bolts:
4 socket head screws M5x50 class 12.9
Tightening torque = 8 Nm
Seals: 4 OR 108; 1 OR 2025/70
Diameter of ports A, B, P, T: Ø 7,5 mm (max)
Diameter of port Y: Ø 3,2 mm (only for /Y option)
V
Mass: 2,8 kg
DLHZO-TE
DLHZO-TES
345
666
Note: for option /B the solenoid and the position transducer are at side of port A
Dotted line =12 poles connector ZH-12P for option /Z
-TE EXECUTION
-TES EXECUTION
ZH-7P or ZM-7P
ZH-5P/BP (for -BP)
ZH-5P (for -PS and -BC)
ZH-7P or ZM-7P
Note: for option /B the solenoid, the position transducer and the integral electronics are at side of port A
345
666
MODEL CODES OF POWER SUPPLY AND COMMUNICATION CONNECTORS (to be ordered separately)
VALVE VERSION
CONNECTOR CODE
ZH-7P ZM-7P ZH-12P
PROTECTION DEGREE
IP65
Power supply Transducer
IP65 IP67 IP67 IP67
-T
-TE, -TES
-TE/Z
-TES /Z, /SF, /SL, /SP
15
connectors supplied with the valve
DATA SHEET
K500 G200, G210, K500
V
= Air bleed off
Dotted line =12 pin connector ZH-12P for options /SF, /SL, /SP, /Z
Dotted line = M8 connector ZH-4P-M8/5 moulded on cable 5 mt lenght for pressure or force transducer (options /SL, /SP)
M8 connector ZH-4P-M8/2-2 moulded with 2 cables, 2 mt lenght for 2 pressure transducers (options /SF)
(1) M8 connector ZH-4P-M8/5 moulded on cable 5 mt lenght for pressure or force transducer (options /SL, /SP)
M8 connector ZH-4P-M8/2-2 moulded with 2 cables, 2 mt lenght for 2 pressure transducers (options /SF)
F180
ZH-5P ZH-5P/BP
IP67 IP67
serial (-PS)
or CANopen (-BC)
PROFIBUS DP (-BP)
ZH-4P-M8/*
(1)
IP67
TES /SF, /SL, /SP
(transducer)
G210, K500
G212, K500
04/13
16 INSTALLATION DIMENSIONS [mm]
Mass: 4,7 kg
Mass: 4,2 kg
DLKZOR-T
DLKZOR-TES
ISO 4401: 2005
Mounting surface: 4401-05-04-0-05
(see table P005)
(for /Y version, surface: 4401-05-05-0-05 without X port)
Fastening bolts:
4 socket head screws M6x40 class 12.9
Tightening torque = 15 Nm
Seals: 5 OR 2050; 1 OR 108
Diameter of ports A, B, P, T: Ø 11,2 mm (max)
Diameter of port Y: Ø 5 mm (only for /Y option)
V
DLKZOR-TE
Mass: 4,7 kg
345
666
MODEL CODES OF POWER SUPPLY AND COMMUNICATION CONNECTORS (to be ordered separately)
VALVE VERSION
CONNECTOR CODE
ZH-7P ZM-7P ZH-12P
PROTECTION DEGREE
IP65
Power supply Transducer
IP65 IP67 IP67 IP67
-T
-TE, -TES
-TE/Z
-TES /Z, /SF, /SL, /SP
17
connectors supplied with the valve
DATA SHEET
K500 G200, G210, K500
345
666
ZH-7P or ZM-7P
ZH-5P/BP (for -BP)
ZH-5P (for -PS and -BC)
ZH-7P or ZM-7P
Note: for option /B the solenoid and the position transducer are at side of port A
Dotted line =12 poles connector ZH-12P for option /Z
-TE EXECUTION
-TES EXECUTION
Note: for option /B the solenoid, the position transducer and the integral electronics are at side of port A
(1) M8 connector ZH-4P-M8/5 moulded on cable 5 mt lenght for pressure or force transducer (options /SL, /SP)
M8 connector ZH-4P-M8/2-2 moulded with 2 cables, 2 mt lenght for 2 pressure transducers (options /SF)
Dotted line =12 pin connector ZH-12P for options /SF, /SL, /SP, /Z
Dotted line = M8 connector ZH-4P-M8/5 moulded on cable 5 mt lenght for pressure or force transducer (options /SL, /SP)
M8 connector ZH-4P-M8/2-2 moulded with 2 cables, 2 mt lenght for 2 pressure transducers (options /SF)
V
= Air bleed off
ZH-5P ZH-5P/BP
IP67 IP67
serial (-PS)
or CANopen (-BC)
PROFIBUS DP (-BP)
ZH-4P-M8/* (1)
IP67
TES /SF, /SL, /SP
(transducer)
G210, K500
G212, K500